5–2
How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter
Publication 1794-6.5.7 – April 1997
Adapter Input Status Word
The input status word consists of:
•
I/O module fault bits – 1 status bit for each slot
•
node address changed – 1 bit
•
I/O status – 1 bit
15
Bit:
0
1
2
3
4
5
6
7
8
10 through 15
I/O Module Fault Bits
Node Address Changed Bit
Slot 0
Slot 1
Slot 2
Slot 3
Slot 4
Slot 5
Slot 6
Slot 7
9
I/O State Bit
Not Used
The adapter input status word bit descriptions are shown in the
following table.
Bit Description
Bit
Explanation
0
This bit is set (1) when an error is detected in slot position 0.
1
This bit is set (1) when an error is detected in slot position 1.
2
This bit is set (1) when an error is detected in slot position 2.
o ul ault
3
This bit is set (1) when an error is detected in slot position 3.
I/O Module Fault
4
This bit is set (1) when an error is detected in slot position 4.
5
This bit is set (1) when an error is detected in slot position 5.
6
This bit is set (1) when an error is detected in slot position 6.
7
This bit is set (1) when an error is detected in slot position 7.
Node Address Changed
8
This bit is set (1) when the node address switch setting has been
changed since power up.
I/O State
9
Bit = 0 – idle
Bit = 1 – run
10 thru 15
Not used – sent as zeroes.
Possible causes for an I/O Module Fault are:
•
transmission errors on the Flex I/O backplane
•
a failed module
•
a module removed from its terminal base
•
incorrect module inserted in a slot position
•
the slot is empty
The node address changed bit is set when the node address switch
setting has been changed since power up. The new node address does
not take affect until the adapter has been powered down and then
powered back up.
Содержание 1794-IT8
Страница 1: ...User Manual Thermocouple Millivolt Input Module Cat No 1794 IT8 Allen Bradley ...
Страница 4: ...soc ii Summary of Changes Publication 1794 6 5 7 April 1997 ...
Страница 8: ...Table of Contents iv Publication 1794 6 5 7 ...
Страница 14: ...Overview of FLEX I O and your Thermocouple mV Module 1 4 Publication 1794 6 5 7 ...
Страница 64: ...Specifications A 10 Publication 1794 6 5 7 March 1997 ...