4–2
Writing Configuration to and Reading Status from your Module with a Remote I/O Adapter
Publication 1794-6.5.7 – April 1997
Individual input channels are configurable to operate with the
following sensor types:
Sensor Type
Range
Voltage
Millivolt
–76.50 to +76.50mV
Thermocouple
Type B
300 to 1800
o
C
r ocoupl
Type E
–230 to 1000
o
C
Type J
–195 to 1200
o
C
Type K
–230 to 1372
o
C
Type R
–50 to 1768
o
C
Type S
–50 to 1768
o
C
Type T
–195 to 400
o
C
Type N
–270 to 1300
o
C
Type C
0 to 2315
o
C
Type L
–175 to 800
o
C
You select individual channel ranges using write words 1 and 2 of
the block transfer write instruction.
Scaling lets you report each channel in actual engineering units.
Scaled values are in integer format.
Input Type
Range
Scaling
Maximum Resolution
Millivolt
–76.50 to +76.50mV
–7650 to +7650
10
µ
V
Type B
300 to 1800
o
C
3000 to 18000
0.1
o
C
Type E
–230 to 1000
o
C
–2300 to 10000
0.1
o
C
Type J
–195 to 1200
o
C
–1950 to 12000
0.1
o
C
Type K
–230 to 1372
o
C
–2300 to 13720
0.1
o
C
Type R
–50 to 1768
o
C
–500 to 17680
0.1
o
C
Type S
–50 to 1768
o
C
–500 to 17680
0.1
o
C
Type T
–195 to 400
o
C
–1950 to 4000
0.1
o
C
Type N
–270 to 1300
o
C
–2700 to 13000
0.1
o
C
Type C
0 to 2315
o
C
0 to 23150
0.1
o
C
Type L
–175 to 800
o
C
–1750 to 8000
0.1
o
C
Type B
572 to 3272
o
F
5720 to 32720
0.1
o
F
Type E
–382 to 1832
o
F
–3820 to 18320
0.1
o
F
Type J
–319 to 2192
o
F
–3190 to 21920
0.1
o
F
Type K
–382 to 2502
o
F
–3820 to 25020
0.1
o
F
Type R
–58 to 3214
o
F
–580 to 32140
0.1
o
F
Type S
–58 to 3214
o
F
–580 to 32140
0.1
o
F
Type T
–319 to 752
o
F
–3190 to 7520
0.1
o
F
Type N
–450 to 2372
o
F
–4500 to 23720
0.1
o
F
Type C
32 to 4199
o
F
320 to 41990
0.1
o
F
Type L
–283 to 1472
o
F
–2830 to 14720
0.1
o
F
Note: In thermocouple mode, scaled number has an implied decimal point 1 digit from the right. For example, if reading is
18000, temperature is 1800.0. In millivolt mode, the implied decimal point is to the left of the last 2 digits. For example, if
reading is 2250, actual reading is 22.50mV
Range Selection
Input Scaling
Содержание 1794-IT8
Страница 1: ...User Manual Thermocouple Millivolt Input Module Cat No 1794 IT8 Allen Bradley ...
Страница 4: ...soc ii Summary of Changes Publication 1794 6 5 7 April 1997 ...
Страница 8: ...Table of Contents iv Publication 1794 6 5 7 ...
Страница 14: ...Overview of FLEX I O and your Thermocouple mV Module 1 4 Publication 1794 6 5 7 ...