Rockwell Automation Publication 1794-IN104C-EN-P - July 2018
15
FLEX I/O 220V AC Digital Input and Output Modules
Relative humidity
IEC 60068-2-30 (Test Db, unpackaged damp heat):
5…95% noncondensing
Vibration
IEC60068-2-6 (Test Fc, operating):
5 g @ 10...500 Hz
Shock, operating
IEC60068-2-27 (Test Ea, unpackaged shock):
30 g
Shock, nonoperating
IEC60068-2-27 (Test Ea, unpackaged shock):
50 g
Emissions
IEC 61000-6-4
ESD immunity
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
1V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
EFT/B immunity
IEC 61000-4-4:
±2 kV @ 5 kHz on power ports
±2 kV @ 5 kHz on signal ports
Surge transient immunity
IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
Conducted RF immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Environmental Specifications
Attribute
Value