Allen-Bradley 1771-P2 Скачать руководство пользователя страница 3

L1

120V ac

L2

EQUIP. GND

SPARE

220/240V ac

120V ac

SPARE

120V 
Operation

11939

L1

L2

EQUIP. GND

SPARE

220/240V ac

120V ac

SPARE

220/240V
Operation

metal jumper

metal jumper

120V ac

ac line

120 V ac 1A SB

220/240 V ac 0.5A SB

Installation Data

Auxiliary Power Supply
Cat. No. 1771P2

4

Before connecting ac power to the power supply, you must:

  check the input voltage
  check the fuse protection

Check the Input Voltage

The power supply is factory-shipped for 120V ac operation.  You can use:

  120V ac

or

  220/240V ac

Two metal jumpers are installed on the front terminal strip at the positions
indicating 120V ac.

ATTENTION: 

Be sure the power supply is correctly jumpered

for

either

 120V ac 

or

 220/240V ac.  Incorrect jumpering on the

terminal strip may cause improper operation or damage to the
power supply.

If you are using the power supply for 220/240V ac operation, remove

 both

metal jumpers on the terminal strip from their original 120V positions.
Install

 one

 of these jumpers at the terminal labeled 220/240V ac.

Check the Fuse Protection

The power supply is protected from overcurrent at its inputs by a
slow-blow fuse.  The power supply comes with one 1A slow-blow fuse
installed for 120V operation.  If you are using the power supply for
220/240V operation, remove the 1A fuse and replace it with the 0.5A
slow-blow fuse that is provided.  Replacement fuses are shown below:

Input Voltage

Fuse

Manufacturer's No.

120V ac

3AG

1A

Bussman:

MDL 1A

Littelfuse:

313001

220/240V ac

3AG
0.5A

Bussman:

MDL 0.5A

Littelfuse:

313.500

A replacement fuse kit (cat. no. 1771-FP) containing both 1A and 0.5A
fuses is available.  Contact your local Allen-Bradley representative for
further information.

Connect AC Power