9pin plugs
1771CE or CD cable
19568
Labels on each plug
identify proper connection.
Auxiliary Power Supply
(Cat. No. 1771-P2)
Installation Data
This document provides information on:
preparing to install the power supply
installing the power supply
connecting ac power to the power supply
power supply output
troubleshooting
specifications
The auxiliary power supply can power one bulletin 1771 I/O chassis
when used with an adapter module, a 1772 Mini-PLC-2
processor, or a
1772 Mini-PLC-2/15
processor.
The auxiliary power supply does not provide battery backup. For battery
backup, use a system power supply (cat. no. 1771-P1).
If You Are Mounting the Power Supply:
Use this Power Cable (Cat. No.):
on the left side of the chassis
1771CE
within 5 cablefeet of the I/O chassis
1771CD
If you mount the power supply on the left side-plate of the I/O chassis,
mount the I/O chassis first (if you have not already done so). See the
Universal I/O Chassis Installation Data
(publication 1771-2.210) for
information on mounting the I/O chassis.
When mounted separately, the power supply can be mounted above or next
to the I/O chassis. It can
not
be mounted below since it is necessary to
allow convection cooling of both the power supply and the I/O chassis.
A minimum vertical distance of six inches should be maintained.
To the Installer
Prepare for Installation
Install the Power Supply and
Connect Backplane Power