Chapter
3
31
Installation
PLC programmable controllers connect directly to the data cartridge
recorder. Other Allen-Bradley products connect to an Industrial Terminal
System (cat. no. 1770-T1,-T2,-T3,-T4), or a 1770-T12 programmer which
provides the interface with the recorder. This section describes both types
of installation. Table 3.A shows the cables used to connect the recorder to
other Allen-Bradley products.
Table 3.A
Cables for Connecting the Data Cartridge Recorder to Other AllenBradley Products
Product Connected to
the Data Cartridge
Recorder
Cable
Cat. No.
PLC
Cassette Recorder Interconnect Cable
1774TD
Industrial Terminal
System
Digital Cassette Recorder Cable
1772TH
PLC4 Microtrol
Digital Cassette Recorder Cable
1772TH
Digital Cassette
Recorder
Digital Cassette Recorder Cable
1772TH
PLC4 Microtrol
Digital Cassette Recorder Cable
1772TH
Series 8200 CND
Cassette Recorder Interconnect Cable
8200CS
Use the following procedure to connect the recorder to PLC
programmable controllers (Figure 3.1).
1. Connect the power cable between the recorder and a grounded 115V
AC outlet.
NOTE: If the recorder has been converted to 230V AC operation, use a
230V AC outlet.
2. Connect a Cassette Recorder Interconnect Cable (cat. no. 1774-TD)
between the recorder and the PLC programmable controller.
Connect the end labeled CASSETTE to the connector labeled A-B
CONTROLLER EQUIPMENT on the recorder. Connect the 41-pin
connector to the Program Panel Interface Module (cat. no. 1774-TB,
-TB2) or the On-line Programming Module (cat. no. 1774-TL2).
General
Connection to PLC
Programmable Controllers