Compact 1769-ASCII Module
31
Publication
1769-IN068B-EN-P - May 2005
Conducted RF Immunity
IEC 61000-4-6:
10 Vrms with 1 kHz sine-wave 80% AM from 150 kHz…80
MHz
Enclosure Type Rating
None (open-style)
Dimensions (HxWxL),
Imperial
3.39 x 1.33 x 4.60 in
Dimensions (HxWxL), Metric
87 x 34 x 118 mm
Serial Port Connectors
Two DB-9 male (with pins)
Conductors Category
2
1
Weight, Imperial
0.4 lb
Weight, Metric
0.18 kg
Certifications (when product
is marked)
c-UL-us
2
- UL Listed for Class I, Division 2 Group A, B, C, D
Hazardous Locations, certified for U.S. and Canada
CE
2
- European Union 89/335/EEC EMC Directive,
compliant with:
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
C-Tick
2
- Australian Radiocommunications Act, compliant
with: AS/NZS CISPR 11; Industrial Emissions
1
Use this conductor category information for planning conductor routing as described in publication
1770-4.1, “Industrial Automation Wiring and Grounding Guidelines.”
2
See the Product Certification link at www.ab.com for Declaration of Conformity, Certificates, and
other certification details.