30
Compact 1769-ASCII Module
Publication
1769-IN068B-EN-P - May 2005
General Specifications
Environmental Conditions
Operational Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0…60
°
C (32…140
°
F)
Storage Temperature
IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating
Thermal Shock): -40…85
°
C (-40…185
°
F)
Relative Humidity
IEC 60068-2-30 (Test Db, Unpackaged Non-operating Damp
Heat):
5…95% non-condensing
Vibration
IEC 60068-2-6 (Test Fc, Operating)
5g @ 10…500 Hz
Operating Shock
IEC 60068-2-27 (Test Ea, Un-packaged Shock): 30g
Non-operating Shock
IEC 60068-2-27 (Test Ea, Un-packaged Shock): 50g
Emissions
CISPR 11:
Group 1, Class A
ESD Immunity
IEC 61000-4-2:
4 kV contact discharges
8 kV air discharges
Radiated RF Immunity
IEC 61000-4-3:
10 V/m with 1 kHz sine-wave 80% AM from 30…2000 MHz
10 V/m with 200 Hz 50% pulse 100% AM from 900 MHz
10 V/m with 200 Hz 50% pulse 100% AM at 1890 MHz
EFT/B Immunity
IEC 61000-4-4:
+2 kV at 5kHz on communications ports
Surge Transient Immunity
IEC 61000-4-5:
+2 kV line-earth (CM) on communications ports