6
Rockwell Automation Publication 1756-IN061B-EN-P - February 2017
Armor ControlLogix Controllers
Product Dimensions
Ground the Controller
You must provide a proper grounding path by using the ground screw on the bottom of the enclosure. To attach grounding wires, remove the screw
and attach a ring lug, or loosen the screw and slide a fork connector underneath. Tighten the screw.
See Industrial Automation Wiring and Grounding Guidelines, publication
1770-4.1
for guidelines on how to install an industrial control system.
PE Ground
Wire Size
Torque
1.3…5.2 mm
2
(#16…#10 AWG)
2 N•m (17.7 lb•in)
240 mm
(9.4 in.)
292 mm
(11.5 in. )
298 mm
(11.7 in.)
215 mm
(8.5 in.)
172 mm
(6.8 in.)
245 mm
(10 in.)
165mm
(6.5 in.)
265 mm
(10.4 in.)
327 mm
(12.9 in.)
550 mm
21.7 in.
32.25 mm
1.3 in.
86.55 mm
3.4 in.
265 mm
10 in.
550 mm
21.7 in.
198.9 mm
7.8 in.
225.75 mm
8.9 in.
Mounting feet in horizontal orientation
Mounting feet in vertical orientation
Clearance for access door opening