Rockwell Automation Publication 1756-RM093J-EN-P - April 2018
29
CIP Safety I/O for the GuardLogix Control System
Chapter 3
Safety Considerations for CIP
Safety I/O Modules
You must commission all devices with a node or IP address and communication
rate, if necessary, before their installation on a safety network.
Ownership
Each CIP Safety I/O module in a GuardLogix system is owned by one
GuardLogix controller. Multiple GuardLogix controllers and multiple CIP
Safety I/O modules can be used without restrictions in chassis or on networks as
needed. When a controller owns an I/O module, it stores the module’s
configuration data, as defined by the user. This controls how the modules operate
in the system.
From a control standpoint, safety output modules can only be controlled by one
controller. Each safety input module is also owned by a single controller;
however, safety input data can be shared (consumed) by multiple GuardLogix
controllers.
Safety I/O Configuration Signature
The configuration signature defines the module’s configuration. It can be read
and monitored. The configuration signature is used to uniquely identify a
module’s configuration. When using a GuardLogix controller, you do not have to
monitor this signature. It is monitored automatically by the GuardLogix
controller. If the configuration signature changes unexpectedly, the CIP safety
connection between controller and I/O module is broken.
I/O Module Replacement
The replacement of safety devices requires that the replacement device be
configured properly and that the replacement device’s operation be user-verified.
ATTENTION:
During replacement or functional testing of a module, the safety
of the system must not rely on any portion of the affected module.
Содержание 1756-L61S ControlLogix 5561S
Страница 10: ...10 Rockwell Automation Publication 1756 RM093J EN P April 2018 Preface Notes...
Страница 64: ...64 Rockwell Automation Publication 1756 RM093J EN P April 2018 Chapter 6 Safety Application Development Notes...
Страница 70: ...70 Rockwell Automation Publication 1756 RM093J EN P April 2018 Chapter 7 Monitor Status and Handle Faults Notes...
Страница 114: ...114 Rockwell Automation Publication 1756 RM093J EN P April 2018 Index Notes...
Страница 115: ......