Rockwell Automation Publication 1734-UM001E-EN-P - July 2013
212
Configure POINT I/O Modules for DeviceNet Networks
•
I/O output status
•
Reset services
•
POINTBus
•
Configuration
3.
At the Groups pull-down menu, select Configuration and the parameters
you want.
4.
Select Single to change or configure parameters one at a time, or All to
change all selections at once, noting that configurable parameters include
the following:
•
Fault Value - Off/on
•
Fault Action - Fault value/hold last state
•
Idle Value - Off/on
•
Idle Action - Idle value/hold last state
•
Enable no load - No load enabled/no load disabled
•
Reset mode - Latch off/auto restart
•
Autobaud - Enable/disable
Note that if autobaud is selected, the communication rate of this module
automatically matches the communication rate of the existing devices on
the network and you are locked out from selecting a communication rate.