Rockwell Automation Publication 1734-UM001E-EN-P - July 2013
Calibrate Your Analog Modules
121
Calibrate the Analog
Current Input Module
To calibrate your current input module, connect the module in a system similar
to that shown in the figure.
1.
Double-click the icon to bring up the General parameter dialog.
IMPORTANT
Apply power to the power supply and module for at least
10 minutes before calibrating the module. This allows
internal temperatures to stabilize, and reduces drift errors.
0
1
0
1
0
1
0
1
0
1
0
1
PDN IE2C
250
Ω
Current Source
DeviceNet Input
Power Supply Voltage
Channel 0
Connect to 0 and 4
Channel 1
Connect to 1 and 5
250
Ω
resistor
protects the current
source in the event
of shorted wires.
0
1
0
1
0
1
0
1
0
1
0
1
0
1
Module
St
a
tus
Network Activity
St
a
tus
Network
St
a
tus
1734-AENT
PointBus
St
a
tus
Field
Power
System
Power
0 2
0
AENT IE2C
EtherNet/IP Input
44037
Current Source
Power Supply Voltage
250
Ω
Channel 0
Connect to 0 and 4
Channel 1
Connect to 1 and 5
250
Ω
resistor
protects the current
source in the event
of shorted wires.
44035
Содержание 1734-OB2
Страница 4: ...Publication 1734 UM001E EN P July 2013 iv Summary of Changes Notes...
Страница 16: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 xxiv Notes...
Страница 22: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 6 About the Modules Notes...
Страница 116: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 118 POINT I O Module Data Notes...
Страница 156: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 158 Troubleshoot with the Indicators Notes...
Страница 168: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 176 Default Data Maps Notes...
Страница 172: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 180 Mounting Dimensions Notes...