Publication 1734-UM002C-EN-P - July 2003
A-2
Specifications
DeviceNet Power Specifications
Power Supply
Note: In order to comply with CE Low Voltage
Directives (LVD), you must use a Safety Extra Low
Voltage (SELV) or a Protected Extra Low Voltage
(PELV) power supply to power this adapter.
Input Voltage Rating
24V dc nominal
DeviceNet Input Voltage Range
11-25V dc DeviceNet specification
Input Overvoltage Protection
Reverse polarity protected
DeviceNet Power Requirements
24V dc (+4% = 25V dc max) @ 30mA maximum
Power Supply Specifications
Power Supply
1
Note:
In order to comply with CE Low Voltage
Directives (LVD), you must use
either a NEC Class 2,
a Safety Extra Low Voltage (SELV) or a Protected
Extra Low Voltage (PELV) power supply to power this
adapter. A SELV supply cannot exceed 30V rms,
42.4V peak or 60V dc under normal conditions and
under single fault conditions. A PELV supply has the
same rating and is connected to protected earth.
Input Voltage Rating
24V dc nominal
10-28.8V dc range
Field Side Power Requirements
24V dc (+20% = 28.8V dc maximum) @ 400mA
maximum
Inrush Current
6A maximum for 10ms
PointBus Output Current
1A maximum @ 5V dc ±5% (4.75 - 5.25
)
Input Overvoltage Protection
Reverse polarity protected
Interruption
Output voltage will stay within specifications when
input drops out for 10ms at 10V with maximum load.
General Specifications
Indicators
3 red/green status indicators
Adapter status
DeviceNet status
PointBus status
2 green power supply status indicators:
System Power (PointBus 5V power)
Field Power (24V from field supply)
Power Consumption
8.1W maximum @ 28.8V dc
Power Dissipation
2.8W maximum @ 28.8V
Thermal Dissipation
9.5 BTU/hr maximum @ 28.8V dc
Isolation Voltage
1250V rms/V ac
Field Power Bus
Nominal Voltage
Supply Voltage Range
Supply Current
24V dc
10-28.8V dc range,
10A maximum
1.
For the 1734-ADN, DeviceNet and user supplied power (I/O power) should be powered from separate
sources. For the 1734-ADNX, because there are three inputs, for CE purposes, the user supplied power must
be separate from the other two (because of surge testing). DeviceNet and the Subnet can be powered from
the same source.
Содержание 1734-ADNX
Страница 1: ...POINT I O DeviceNet Adapter 1734 ADN 1734 ADNX User Manual...
Страница 4: ...Publication 1734 UM002C EN P July 2003 Summary of Changes 2 Notes...
Страница 14: ...Publication 1734 UM002C EN P July 2003 Table of Contents iv...
Страница 80: ...Publication 1734 UM002C EN P July 2003 A 4 Specifications Notes...
Страница 112: ...Publication 1734 UM002C EN P July 2003 B 32 1734 ADNX Quick Start Notes...
Страница 128: ...Publication 1734 UM002C EN P July 2003 D 14 Default Data Maps...
Страница 135: ......