16
Rockwell Automation Publication 1608S-UM001C-EN-P - November 2018
Chapter 3
Installation
5.
Verify that the JP1 plug is properly configured, per
Table 4
: The plug with
RED wires must be installed if the channel voltage is greater than
250V AC.
6.
Replace the right-side cover and tighten the two screws.
Nominal Voltage
Configurations
WARNING:
This unit is not rated for 600V AC or 690V AC L-L installations.
600Y/346V installations require 4-wire L-N wiring method. The neutral must be
connected as shown in
Table 5
.
Table 4 - Nominal Voltage Configurations (shipped standard with 480V (L-L)
Your Voltage
Nominal
Volts per
Channel
(2)
Channels
Mains
Wires
Wiring
Diagram
Table 2 on
page 11
Power Supply
Jumper JP1
Any single-phase voltage ≤240V
nominal
1
2
S1
White wires
100 (L-N for 100/200V split-phase)
100
2
3
S2
White wires
105 (L-N for 105/210V split-phase)
105
2
3
S2
White wires
110 (L-N for 190Y/110V 3-phase)
110
3
4
LN
White wires
115 (L-N for 200Y/115V 3-phase)
115
3
4
LN
White wires
115 (L-N for 115/230V split-phase)
115
2
3
S2
White wires
120 (L-N for 208Y/120V 3-phase)
120
3
4
LN
White wires
120 (L-N for 120/240V split-phase)
120
2
3
S2
White wires
125 (L-N for 216Y/125V 3-phase)
125
3
4
LN
White wires
127 (L-N for 220Y/127V 3-phase)
127
3
4
LN
White wires
133 (L-N for 230Y/133V 3-phase)
133
3
4
LN
White wires
139 (L-N for 240Y/139V 3-phase)
139
3
4
LN
White wires
190 (L-L for 190Y/110V 3-phase)
190
3
3
LL
White wires
200 (L-L for 100/200V split-phase)
200
1
2
S1
White wires
208 (L-L for 208Y/120V 3-phase)
208
3
3
LL
White wires
210 (L-L for 105/210V split-phase)
210
1
2
S1
White wires
216 (L-L for 216Y/125V 3-phase)
216
3
3
LL
White wires
220 (L-L for 380Y/220V 3-phase)
220
3
3
LL
White wires
230 (L-L for 230Y/133V 3-phase)
230
3
3
LL
White wires
230 (L-N for 400Y/230V 3-phase)
230
3
4
LN
White wires
240 (L-L for 120/240V split-phase)
240
3
3
LL
White wires
240 (L-N for 415Y/240V 3-phase)
240
3
4
LN
White wires
254
(1)
(L-N for 440Y/254V 3-phase)
254
3
4
LN
Red wires
277 (L-N for 480Y/277V 3-phase)
277
3
4
LN
Red wires
346 (L-N for 600Y/346V 3-phase)
346
3
4
LN
Red wires
346 (L-L for 346Y/200V 3-phase)
346
3
3
LL
Red wires
380 (L-L for 380Y/220V 3-phase)
380
3
3
LL
Red wires
400 (L-L for 400Y/230V 3-phase)
400
3
3
LL
Red wires
400 (L-N for 690Y/400V 3-phase)
400
3
4
LN
Red wires
Содержание 1608S-3V480E