All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM043A-EN-P — March 2014

23

Bulletin 1606 Switched Mode Power Supplies

22.9. Charging Batteries 

The power supply can be used to charge lead-acid or maintenance free batteries. (Four 12V batteries in series) 

Instructions for charging batteries: 

a)

Set output voltage (measured at no load and at the battery end of the cable) very precisely to the end-of-charge 
voltage. 

End-of-charge voltage 

55.6V 

55.0V 

54.3V 

53.6V 

Battery temperature 

10°C 

20°C 

30°C 

40°C 

b)

Use a 15A or 16A circuit breaker (or blocking diode) between the power supply and the battery. 

c)

Ensure that the output current of the power supply is below the allowed charging current of the battery. 

d)

Use only matched batteries when putting 12V types in series. 

e)

The return current to the power supply (battery discharge current) is typ. 7mA when the power supply is switched 
off (except if using a blocking diode). 

22.10. Operation on Two Phases

 

240V 

+10%

 max.

L2

L1

L3

L

N

PE

Power Supply

AC

DC

internal

fuse

The power supply can also be used on two phases of a three-phase-system. 
Such a phase-to-phase connection is allowed as long as the supplying 
voltage is below 240V

+10%

22.11. Use in a Tightly Sealed Enclosure

 

When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher 
than outside. In such situations, the inside temperature defines the ambient temperature for the power supply. 

The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure. 

The power supply is placed in the middle of the box, no other heat producing items are inside the box  

Enclosure: 

 

 

Rittal Typ IP66 Box PK 9522 100, plastic, 254x180x165mm 

Load: 

 

   48V, 

8A; 

(=80%) 

load 

is 

placed 

outside 

the 

box 

Input:  

 

 

230Vac 

Temperature inside enclosure:  

53.3°C (in the middle of the right side of the power supply with a distance of 2cm) 

Temperature outside enclosure:   25.3°C 
Temperature rise: 

 

28.0K 

Содержание 1606-XLC

Страница 1: ...22 22 8 Inductive and Capacitive Loads 22 22 9 Charging Batteries 23 22 10 Operation on Two Phases 23 22 11 Use in a Tightly Sealed Enclosure 23 22 12 Mounting Orientations 24 PE and symbol PE is the...

Страница 2: ...usly at temperatures up to 45 C Additionally the 1606 XLE480FP can deliver about 4 times the nominal output current for 15ms which helps to trip fuses on faulty output branches High immunity to transi...

Страница 3: ...uct airflow and do not cover ventilation grid e g cable conduits by more than 30 Keep the following installation clearances 40mm on top 20mm on the bottom 5mm on the left and right sides are recommend...

Страница 4: ...33A at 48V 10A see Fig 3 3 Power factor typ 0 99 0 99 0 95 at 48V 10A see Fig 3 4 Crest factor typ 1 5 1 5 1 65 at 48V 10A Start up delay typ 850ms 850ms 650ms see Fig 3 2 Rise time typ 90ms 90ms 90ms...

Страница 5: ...he input inrush current after turn on of the input voltage and after short input voltage interruptions The charging current into EMI suppression capacitors is disregarded in the first microseconds aft...

Страница 6: ...nom 480W continuously available nom 576W Power Boost Overload behaviour cont current output voltage 25Vdc see Fig 6 1 HiccupPLUS mode output voltage 25Vdc see Fig 6 1 Short circuit current min 18A loa...

Страница 7: ...24 56V 32 40 48 20A 7 5 2 5 5 10 15 17 5 Adjustment Range Output Current Continuous current Factory setting Hiccup mode Output Voltage Parallel Use typ 42V 0 4 8 44V 46V 48V 56V 50V 52V 54V 12A 10 6 2...

Страница 8: ...48V 10A min 5 Hold up Time Zero Transition Output Voltage Input Voltage 8 DC OK Relay Contact This feature monitors the output voltage which is produced by the power supply itself It is independent o...

Страница 9: ...mption for a typical application where the power supply is loaded with 25 of the nominal load for 25 of the time 50 of the nominal load for another 25 of the time 75 of the nominal load for another 25...

Страница 10: ...the built in electrolytic capacitors Lifetime expectancy is specified in operational hours and is calculated according to the capacitor s manufacturer specification The manufacturer of the electrolyt...

Страница 11: ...t applicable Instructions a Use appropriate copper cables that are designed for minimum operating temperatures of 60 C for ambient up to 45 C and 75 C for ambient up to 60 C minimum 90 C for ambient u...

Страница 12: ...t the output voltage Factory set 48 0V D DC OK LED green On when the output voltage is 90 of the adjusted output voltage E DC OK Relay Contact quick connect spring clamp terminals The DC OK relay cont...

Страница 13: ...0Vac 200ms 140Vac 500ms Criterion A Criterion C Criterion A Criterion A Criterion A Criterion A Voltage interruptions EN 61000 4 11 0 of 200Vac 0V 5000ms Criterion C Voltage sags SEMI F47 0706 dips on...

Страница 14: ...reduce output power or ambient temperature see Fig 15 2 IEC 62103 EN 50178 overvoltage category II Altitude de rating 30W 1000m or 5 C 1000m 2000m 6500ft see Fig 15 2 Over voltage category III IEC 62...

Страница 15: ...rews small parts Over temperature protection yes Output shut down with automatic restart Input transient protection MOV Metal Oxide Varistor Internal input fuse included not user replaceable In case o...

Страница 16: ...ions in which a load starts unexpectedly or cannot be switched off when unnoticed ground faults occur B When testing input to DC OK ensure that the max voltage between DC OK and the output is not exce...

Страница 17: ...17 Bulletin 1606 Switched Mode Power Supplies 20 Physical Dimensions and Weight Weight 1000g 2 2lb DIN Rail Use 35mm DIN rails according to EN 60715 or EN 50022 with a height of 7 5 or 15mm The DIN r...

Страница 18: ...s run in time unless noted otherwise 18 Rockwell Automation Publication 1606 RM043A EN P March 2014 Bulletin 1606 Switched Mode Power Supplies 21 Accessories 21 1 1606 XLC Wall Mounting Bracket This b...

Страница 19: ...r and the built in large sized output capacitors of the power supply The capacitors get discharged during such an event which causes a voltage dip on the output The following two examples show typical...

Страница 20: ...ed the wiring is considered as thermally safe wether the MCB opens or not To avoid voltage dips and under voltage situations in adjacent 48V branches which are supplied by the same source a fast magne...

Страница 21: ...higher than the current of one unit Keep an installation clearance of 15mm left right between two power supplies and avoid installing the power supplies on top of each other Do not use power supplies...

Страница 22: ...when the sum of the output voltage is above 60Vdc Avoid return voltage e g from a decelerating motor or battery which is applied to the output terminals Keep an installation clearance of 15mm left ri...

Страница 23: ...urrent is typ 7mA when the power supply is switched off except if using a blocking diode 22 10 Operation on Two Phases 240V 10 max L2 L1 L3 L N PE Power Supply AC DC internal fuse The power supply can...

Страница 24: ...urrent Curve A2 Max allowed output current results in approximately half the lifetime expectancy of A1 Fig 22 4 Mounting Orientation A Standard orientation Power Supply OUTPUT INPUT Output Current 0 1...

Страница 25: ......

Страница 26: ...ial help in getting your product up and running New Product Satisfaction Return Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manuf...

Отзывы: