All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
10
Rockwell Automation Publication 1606-RM043A-EN-P — March 2014
Bulletin 1606 Switched Mode Power Supplies
10. Lifetime Expectancy and MTBF
AC
100V
AC 120V
AC 230V
Lifetime expectancy
*)
146
000h
*)
152
000h
*)
168
000h
*)
at 48V, 5A and 40°C
413
000h
*)
430
000h
*)
475
000h
*)
at 48V, 5A and 25°C
65 000h
70 000h
87 000h
at 48V, 10A and 40°C
184
000h
*)
198
000h
*)
246
000h
*)
at 48V, 10A and 25°C
38 000h
43 000h
60 000h
at 48V, 12A and 40°C
107
000h
*)
122
000h
*)
170
000h
*)
at 48V, 12A and 25°C
MTBF
**)
SN 29500, IEC 61709
468 000h
484 000h
537 000h
at 48V, 10A and 40°C
770 000h
796 000h
882 000h
at 48V, 10A and 25°C
MTBF
**)
MIL HDBK 217F
254 000h
261 000h
290 000h
at 48V, 10A and 40°C;
Ground Benign GB40
355 000h
361 000h
395 000h
at 48V, 10A and 25°C;
Ground Benign GB25
56 000h
57 000h
64 000h
at 48V, 10A and 40°C;
Ground Fixed GF40
75 000h
77 000h
86 000h
at 48V, 10A and 25°C;
Ground Fixed GF25
*) The
Lifetime expectancy
shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime
expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the
capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years
(131 400h). Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices.
**)
MTBF
stands for
M
ean
T
ime
B
etween
F
ailure, which is calculated according to statistical device failures, and indicates reliability of a
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that
statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it cannot be determined if the failed unit
has been running for 50 000h or only for 100h.
11. Functional Diagram
Fig. 11-1
Functional diagram
+
+
-
-
Output
Over-
Voltage
Protection
PFC
Converter
Output
Voltage
Regulator
Power
Converter
Output
Filter
Output
Voltage
Monitor
Output
Power
Manager
Temper-
ature
Shut-
down
Input Fuse
Input Filter
Input Rectifier
Active Inrush Limiter
V
OUT
L
N
DC-ok
Contact
DC-ok
LED
Single /
Parallel
DC-ok
Relay