Rockwell Automation Publication 1606-RM111A-EN-P - July 2020
7
Input and Output
Characteristics
, the power supplies can be either 1606-XLX120 or 1606-XLX240. The
redundancy module is 1606-XLBRED20.
Power Losses
Figure 5 - Power Losses at 25 °C (77 °F)
Attributes
Values
Notes
Number of inputs
—
2
—
Number of outputs
—
1
—
Input voltage
Nom
DC 12…28V ±25%
—
Input voltage range
—
9…35V DC
—
Voltage drop, input to output
Typ
0.46V
at 2 x 5 A, see
Typ
0.56V
at 2 x 10 A, see
Input current
Nom
2 x 0…10 A
continuous
Nom
2 x 10…16 A
for 5 s
Peak input current
Max
1000 A
for 10 ms max per input
Output current
Nom
20 A
continuous
Nom
20…32 A
for 5 s
Max
26 A
(1)
(1)
Ensure that the continuous output current does not exceed 26 A. Check the short-circuit current of the power sources and if
the power source can deliver more than 26 A together, use an appropriate fuse on the output.
at continuous overload or short circuit
Reverse current
Max
4 mA
per input, -40…+70 °C (-40…+158 °F)
Reverse voltage
Max
45V DC
voltage applied to the output, continuously allowed
Figure 3 - Input to Output Voltage Drop
Figure 4 - Test Setup For Voltage Drop Measurements
Voltage Drop, Typ
100 mV
200 mV
300 mV
400 mV
500 mV
600 mV
5 A
15 A
20 A
10 A
Output:
2x5 A
2x2.5 A
Input:
2x10 A
2x7.5 A
0
0
Input, Output Current
A ... 25 °C
B... 60 °C
A
B
V
A
Power Supply
24V, 5 A or
24V, 10 A
+
-
V
A
I
1
I
2
U
1
U
2
I
1
I
2
=
U
2
U
1
=
Voltage Drop
U
1
=
U
OUT
-
Output
A
V
I
OUT
U
OUT
Variable
Load,
0…20 A
Redundancy Module
Input 1
Input 2
Output
Power Supply
24V, 5 A or
24V, 10 A
+
-
Attribute
Values
Notes
Power losses
—
0 W
at no load (stand-by)
Typ
4.6 W
at 24V and 2 x 5 A input current
Typ
11.2 W
at 24V and 2 x 10 A input current
Power Losses, Typ
0
0
5
10
2
4
6
8
10
12 W
20 A
15
Output Current