Allen-Bradley 1606-XLBRED20 Скачать руководство пользователя страница 14

14

Rockwell Automation Publication 1606-RM111A-EN-P - July 2020

           

Using Only One Input 
Instead of Both Channels

You can use only one input instead of both up to a nominal input current of 
20 A at 55 °C (131 °F) max ambient temperature. However, it is always 
recommended to connect both input path in parallel for reduced power losses 
and voltage drop. In cases when this is not possible, the following values can be 
expected:

In 

Figure 1

 the redundancy module is used with a 1606-XLB480E power supply.

Recommendations for 
Redundancy

Recommendations for the configuration of redundant power systems:

Use three-phase power supplies to gain functional safety if one phase 
fails.

When single-phase power supplies are used, connect them to different 
phases or mains circuits if possible.

Use separate input fuses for each power supply.

Set the power supply in “Parallel-Use” mode if this feature is available.

It is desirable to set the output voltages of all power supplies to the same 
value.

Inductive and Capacitive 
Loads

The unit is designed to supply any kind of loads, including unlimited 
capacitive and inductive loads.

Attributes

Values

Notes

Voltage drop, input to output

Typ

585 mV

at 1 x 10 A, 25 °C (77 °F), see 

Figure 12

Typ

645 mV

at 1 x 20 A, 25 °C (77 °F), see 

Figure 12

Power losses

0 W

at 0 A, 25 °C (77 °F)

Typ

5.85 W

at 10 A, 25 °C (77 °F)

Typ

12.9 W

at 20 A, 25 °C (77 °F)

Figure 12 - Input to Output Voltage Drop When Only One Input is Used

Figure 13 - Test Setup for Voltage Drop Measurements

Voltage Drop, Typ

200 mV

300 mV

400 mV

500 mV

600 mV

700 mV

5 A

15 A

20 A

10 A

0

Input, Output Current

A ... 25 °C

B... 60 °C

A

B

 

V

A

Power Supply

24V, 20 A

+

-

I

1

U

1

Voltage Drop

U

1

=

U

OUT

-

Output

A

V

I

OUT

U

OUT

Variable

Load,
0…20 A

Redundancy Module

Input 1

Input 2

Output

Input 2
must not
be used

 

Содержание 1606-XLBRED20

Страница 1: ...DualInputRedundancyModule DC 12 28V 20 A Catalog Number 1606 XLBRED20 Reference Manual Original Instructions...

Страница 2: ...kwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permissi...

Страница 3: ...Diagram 9 Front Side and User Elements 9 Electromagnetic Compatibility 10 Environment 11 Protection Features 11 Safety Features 12 Dielectric Strength 12 Approvals 12 Standards 12 Physical Dimensions...

Страница 4: ...4 Rockwell Automation Publication 1606 RM111A EN P July 2020 Notes...

Страница 5: ...most failures in a single power supply The two power supply outputs should be isolated from each other by using diodes or other switching arrangements For example two 10 A power supplies are needed t...

Страница 6: ...can cause controller failures Product features Cost effective solution to build redundant systems Dual input with single output Two diodes common cathode DC 12 28V 25 wide range input Full power from...

Страница 7: ...of the power sources and if the power source can deliver more than 26 A together use an appropriate fuse on the output at continuous overload or short circuit Reverse current Max 4 mA per input 40 70...

Страница 8: ...817 000 h at 24V and 40 C 104 F Ground Fixed GF40 2 709 000 h 2 782 000 h at 24V and 25 C 77 F Ground Fixed GF25 3 675 000 h 3 707 000 h at 24V and 40 C 104 F Ground Benign GB40 5 620 000 h 5 674 000...

Страница 9: ...tional Diagram Figure 6 Functional Diagram Front Side and User Elements Input 1 Input 2 Output Surge Protection Surge Protection Surge Protection Figure 7 Front Side User Elements 1 Input terminals fo...

Страница 10: ...on A earthed DIN rail 1 kV Criterion A Conducted disturbance on input lines EN 61000 4 6 0 15 80 MHz 20V Criterion A Conducted disturbance on output lines EN 61000 4 6 0 15 80 MHz 20V Criterion A Powe...

Страница 11: ...ne or other LABS critical substances and is suitable for use in paint shops 1 Operational temperature is the same as the ambient temperature and is defined as the air temperature 2 cm 0 79 in below th...

Страница 12: ...ndicates conformance with the EMC Directive IEC 60950 1 CB Scheme Information Technology Equipment UL 508 Listed for use as Industrial Control Equipment U S A UL 508 and Canada C22 2 No 107 1 01 E Fil...

Страница 13: ...ht of 7 5 mm 0 295 in or 15 mm 0 59 in Plastic Material of Housing Flame retardant Polycarbonate PC UL94 V0 Vicat softening temperature specified with 149 C 300 F according to ASTM D1525 Installation...

Страница 14: ...e separate input fuses for each power supply Set the power supply in Parallel Use mode if this feature is available It is desirable to set the output voltages of all power supplies to the same value I...

Страница 15: ...sensitive loads as shown in Figure 14 With the 1606 XLBRED20 redundancy module the power supply for the demanding loads can be used as a redundant source to supply the controls as shown in Figure 15...

Страница 16: ...Redundancy up to 20 A requires two 20 A power supplies and two 1606 XLBRED20 redundancy modules Use separate mains systems for each power supply whenever it is possible The power supply in Figure 16...

Страница 17: ...res and Contact Ratings Specifications publication IC TD002 Provides a quick reference tool for Allen Bradley industrial automation controls and assemblies Safety Guidelines for the Application Instal...

Страница 18: ...owledgebase Access Knowledgebase articles rok auto knowledgebase Local Technical Support Phone Numbers Locate the telephone number for your country rok auto phonesupport Literature Library Find instal...

Отзывы: