2

!

 !!  

2–1

 !!  !

Take these actions to prolong controller life and
performance:

D

store within an ambient temperature range of
–40

_

 to +85

_

C

D

store within a relative humidity range of 0%
to 95%, non-condensing

D

protect the cooling fan by avoiding dust or
metallic particles

D

avoid storing or operating the controller where
it could be exposed to a corrosive atmosphere

D

protect from moisture and direct sunlight

D

operate at an ambient temperature range of 0

_

to +50

_

C

To maintain proper working conditions, install the
controller on a flat, vertical and level surface. Use
mounting screws up to 4.5mm (0.177 inches) in
diameter or mount on 35mm DIN Rail.

  !#  

This product complies with Electromagnetic
Compatibility (EMC) Directive 89/336/EEC,
when the following requirements for a
conforming installation are applied:

D

an input line filter must be installed to reduce
conducted emissions.  Refer to the accessory
list in Appendix A.  When using the filters
listed in Appendix A, the maximum motor
cable lengths are 75m (250 feet) for 230V
controllers and 40m (133 feet) for 460V
controllers.

D

the controller system must be mounted in a
shielded enclosure to reduce radiated
emissions.  A typical NEMA or IEC metal
enclosure is adequate.

D

motor cables must be in grounded metal
conduit, or have shielding/armor with
equivalent attenuation to reduce radiated
emissions.

D

control and signal wiring must be in grounded
metal conduit or have shielding with
equivalent attenuation.

$ !  !# 

This product complies with Low Voltage
Directive 72/23/EEC when conforming with the
following installation requirements:

D

review the General Precautions section on
page 1–1, inside front cover, and other
ATTENTION statements throughout this
manual prior to installation of the controller.

D

the controller is intended to be installed with a
fixed connection to the earth. The use of
residual-current-operated protective devices
(RCDs) or ground fault indicators is not
recommended. If unavoidable, the Bulletin
160 is compatible with type B RCDs only.

D

the controller should be installed in an
appropriate or suitable enclosure.

Important:  The conformity of this controller and
filter to any standard does not guarantee that the
entire installation will conform.  Many factors can
influence the total installation and only direct
measurements can verify total conformity.

A copy of the Declaration of Conformity (DOC)
is available from your local Rockwell Automation
sales office.

"! "! 

  !

!

 

" "  "&&  

 !!

 "

#("'" & %)&

! * 

  

#("'" #%$(

  '#  !    "

D

See Appendix A for details on controller
dimensions and weights.

D

There must be a minimum of 12.5mm
(0.5 inches) clearance around all sides of the
controller.  Use either DIN rail or mounting
holes. (Use the drilling template at the back of
the manual for mounting the controller.)

D

Leave debris cover attached during controller
installation to protect from falling debris.  To
ensure proper controller operation, remove
cover before applying power.

Содержание 160 SSC

Страница 1: ...160 SSC Variable Speed Controller Series B 0 37 2 2 kW 1 2 3 HP FRN 5 xx Allen Bradley Installation Manual Table of Contents Index spl_en_b fm5 Page 1 Monday September 15 1997 1 31 PM...

Страница 2: ...or liability for actual use based upon the illustrative uses and applications No patent liability is assumed by Rockwell Automation with respect to use of information circuits or equipment described...

Страница 3: ...rldwide representation Argentina Australia Austria Bahrain Belgium Bolivia Brazil Bulgaria Canada Chile China People s Republic of Colombia Costa Rica Croatia Cyprus Czech Republic Denmark Dominican R...

Страница 4: ...ial Requirements for a Conforming EMC Installation 1 An input line filter module see Accessories in Appendix A must be installed to reduce conducted emissions When using the filters listed in Appendix...

Страница 5: ...es or separate conduit Cable Clamps Use suitable EMC tested cable clamps only Theconnectionareamustbe360degreesaroundtheshieldedcable The cable clamps also provide strain relief for the cable When usi...

Страница 6: ...nclosure anEMC tested cable clamp or metal conduit must be used to solidly connect the cable shield to the enclosure Theshieldonthemotorsidemustbesolidlyconnectedtothemotor housing with an EMC tested...

Страница 7: ...able worldwide a global network of system solutions providers and the advanced technology resources of Rockwell Worldwide representation Argentina Australia Austria Bahrain Belgium Bolivia Brazil Bulg...

Страница 8: ...aining a constant motor shaft speed under heavy loading conditions D Configurable Terminal Block Input The parameter P46 Input Mode has been expanded to provide greater flexibility New input modes inc...

Страница 9: ...ii This Page Intentionally Blank...

Страница 10: ...lower Model 2 7 Control Wiring Preset Speed Model 2 7 Control Wiring Diagrams 2 8 Features 3 1 Display Mode 3 1 Program Mode 3 1 Removing Program Keypad Module 3 2 Start up Procedure Analog Signal Fol...

Страница 11: ...ii This Page Intentionally Blank...

Страница 12: ...TTENTION This controller contains ESD Electrostatic Discharge sensitive parts and assemblies Static control precautions are required when installing testing servicing or repairing this assembly Compon...

Страница 13: ...T160 AA04NSF1P1 SER B I N P U T V A Hz VA O U T P U T V A Hz 3 Motor Rating 200 240 5 4 50 60 2200 200 230 4 5 0 240 0 75kW 1HP ALLEN BRADLEY MADE IN U S A Nameplate is located on the side of the unit...

Страница 14: ...issions D control and signal wiring must be in grounded metal conduit or have shielding with equivalent attenuation This product complies with Low Voltage Directive 72 23 EEC when conforming with the...

Страница 15: ...k One TB1 S T L3 L2 L1 BR BR R T1 T2 T3 V DC DC U W Terminal Block Two TB2 Required Branch Circuit Disconnect Dynamic Brake Module Option Capacitor Module Option Input Line Protective Device 2 1 1 2 1...

Страница 16: ...sized to handle the total current of the branch circuit Power Line Condition Corrective Action Low Line Impedance less than 1 line reactance Line Reactor See A 4 or Isolation Transformer Line has powe...

Страница 17: ...ting The controller should be installed as close to the motor as possible Important Both Reflected Wave and Capacitive Current Considerations need to be taken into account when determining motor cable...

Страница 18: ...4 320 98 650 198 300 91 300 91 0 75 kW 1 HP 4 300 91 300 91 300 91 600 183 300 91 300 91 1 HP 8 300 91 300 91 300 91 550 168 300 91 300 91 2 300 91 375 114 320 98 600 183 300 91 300 91 0 55 kW 0 75 HP...

Страница 19: ...iquid gas or solids exist an additional hardwired stop circuit is required to remove AC line power to the drive When AC input power is removed there will be a loss of inherent regenerative braking eff...

Страница 20: ...ed Relay Common Normally Open Signal Specification Terminal TB3 FAULT READY Figure 2 3 TB3 Control Wiring for Analog Signal Follower Model FAULT READY 8 7 6 5 4 3 2 1 9 1 10 1 SW1 SW2 Common SW3 Rever...

Страница 21: ...actory Default Setting Specification 8 7 6 5 Reverse Start Common Stop Signal Terminal TB3 Important After a Stop input the Start input must be toggled to Run again Figure 2 6 TB3 Two Wire Run Forward...

Страница 22: ...10 TB3 Two Wire Local Remote control Setting 6 Specification 8 7 6 5 Run Reverse Run Forward Local Remote Common Signal Terminal TB3 Figure 2 11 Input Mode Setting TB3 8 Open TB3 8 Closed 4 Accel 2 De...

Страница 23: ...2 10...

Страница 24: ...gramming controller parameters D three keys for control inputs to the controller D directional LEDs D a 6 digit seven segment LED display The controller always powers up in the display mode While in t...

Страница 25: ...tains ESD Electrostatic Discharge sensitive parts and assemblies Static control precautions are required when installing testing servicing or repairing this assembly Component damage may result if ESD...

Страница 26: ...9 4397411 7 8 389 11 5 7 3897 9 438 4 91 3 3 59 7 3 1 3 3 0 0 4 0 4 1 0 0 0 0 0 0 4 59 7 574 8 4257 38 8 7 59 43 4 11 4397411 7 5 7 2 9 78 9 947 19 8 99 3 8 4 7 4397411 7 8 6 55 9 74 7 2 5 4 1 9 8 5 7...

Страница 27: ...1 0 1 210 1 1 1 1 1 1 1 1 1 1 6 0 11 1 2 6 0 2 1 10 2 0 11 6 2 20 6 2 3 6 1 1 1 0 2 1 6 2 20 0 6 3 6 1 1 1 21 1 0 1 0 1 4 6 0 1 0 2 1 1 1 0 1 12 1 1 1 1 0 1 1 1 1 1 1 0 1 12 0 1 0 1 21 4 1 1 0 002 1...

Страница 28: ...7 0 2 0 1 0 2 2 2 1 1 02 1 7 2 2 0 1 2 0 5 0 0 2 2 2 2 0 2 5 1 6 2 0 0 12 1 0 3 0 2 0 2 0 1 22 2 1 6 0 2 0 1 0 21 2 07 3 2 1 22 1 1 2 1 1 0 2 2 0 0 6 2 0 0 7 3 1 7 0 0 71 0 1 2 4 3 1 2 0 2 07 3 2 1 2...

Страница 29: ...1 6 1 6 03 52 5 6 176276 744 06 24 5 06 6 6 4 0 5 0 0 61 5 10641 4 6 76276 744 06 25 04 52 5 6 176276 219 4 24 5 06 6 6 4 0 5 0 0 61 5 6 10641 4 76276 19 4 05 52 5 6 75 1 6 8 61 61 1 6 06 52 5 6 4 37...

Страница 30: ...B3 6 Bit 3 Polarity Input Mode 2 Keypad 5 027 2 03 4 6 0 154 4 6 0 154 40 28 5 2 13 Power Factor Angle 31 83 4 42 2 3 47 0402 60 4 0402 522 4 40 2 3 14 Memory Probe Display 3 8 0 7 540 4 0 3 26 1 230...

Страница 31: ...12 0 3 7 2 2 20 0 5 32 32 2 3 31 7 2 8 8 33 12 0 3 7 2 20 0 5 32 32 1 0 2 0 2 5 03 2 8 8 34 2 0 1 12 31 7 2 20 0 5 12 1 2 2 0 2 2 0 1 2 2 12 2 2 2 0 2 0 5 32 32 2 0 5 2 32 1 32 5 0 1 2 1 1 12 0 2 0 6...

Страница 32: ...5 5 Program Group P Parameter Description 0 37 0 38 2 0 y b 0 39 0 0 0 0 0 1 b y 0 1 0 0 a 1 2 2 40 0 0 0 0 0 0 2 0 1 2 2...

Страница 33: ...5 6 Program Group P Parameter Description 41 0 4 2 42 43 2 1 44 1 1 3 3 45 0 1 3 3 2 0 1...

Страница 34: ...Output Configure 2 0 1 6 21 21 2 1 16 Settings 0 Controller Ready Faulted 1 At Frequency 2 Controller Running 3 Reverse 4 Motor Overload 5 Ramp Regulated 7 Above Current 6 Above Frequency Output chan...

Страница 35: ...3 8 7 4397411 7 5 7 47A 2 3 94 0 0 50 2 2 3 2 7 4 9 2 8 9 4397411 7 11 99 259 94 7 8 9 19 94 2 7 1 51 2 9 3 7 89 79 99 2598 94 43 8 43 8 52 3 1 8 8 1 8 9 73 1 3 2 7 0 3 99 3 8 1 99 3 8 9 74 9 1 7 0 3...

Страница 36: ...3 5 9 304 a a a a a a 9 304 304 0 6 8 304 1 22 0 2 304 6 1 1 304 22 1 6 3 304 2 1 1 9 1 304 22 3 0 3 54 22 2 1 0 2 0 2 8 0 0 1 3 2 0 1 2 2 3 2 0 1 2 3 2 1 2 2 4 3 1 32 2 7 1 2 2 8 1 0 2 0 2 0 0 5 2 2...

Страница 37: ...3 4 55 0 8 0 63 645 3 5 165 50 5 0 530 3 503 6 54 50 8 3 0 530 64 1 0 530 1 3 5 3 4 55 50 50 3 130 3 1 0 530 50 6 3 6 57 4 5 50 5 4 1 3 5 3 1305 54 0 530 3 1 3 5 34 30 6 65 03 1 340 50 6 3 6 58 4 4 5...

Страница 38: ...l Time 2 P33 Maxi mum Frequency P53 S Curve 70 Decel Time 2 P33 Maximum Frequency P53 S Curve Preset Accel Decel Chart For Preset Speed Model Only TB3 4 SW3 TB3 2 SW2 TB3 1 SW1 Preset Accel Decel P30...

Страница 39: ...0 4 01 7 0 2 32 2 32 2 7 0 1 0 2 2 4 32 0 4 01 1 2 0 3 7 5 8 0 0 3 0 3 7 3 0 2 0 4 01 321 3 25 5 0 9 3 4 01 5 0 5 2 0 4 01 1 2 3 0 4 3 74 3 0 32 2 0 32 2 2 0 32 1 2 2 0 4 01 321 7 2 0 1 0 0 0 2 25 5...

Страница 40: ...d correct the fault as well as the condition that caused the fault To clear a fault perform one of the following D Press the program keypad s stop button D Cycle power to the controller D Cycle the in...

Страница 41: ...6 2...

Страница 42: ...2 3 1 1 8 1 04 8 2 41 0 D 1 8 3 3 1 04 8 2 2 1 2 3 3 3 1 2 2 D 1 8 3 3 1 2 3 1 04 2 1 2 3 1 1 8 31 43 2 2 D 1 8 3 3 1 11 3 1 3 3 13 3 3 3 1 1 3 1 2 33 2 D 1 8 3 3 0 2 2 6 2 1 1 04 8 2 41 D 1 8 3 3 0...

Страница 43: ...B3 7 or Potentiometer or Opto Isolator C P U Relay Circuitry Program Keypad Module Motor T1 U T2 V T3 W GND PE Current Circuitry Bus Voltage Circuitry Control Power Fault Feedback DC DC BR BR Customer...

Страница 44: ...at is unique to each SSC Controller rating Table A 3 contains information that applies to all Controller ratings 0 0 10 10 1 0 4 3 0 00 10 0 1 5 6 0 7 10 0 2 0 0 40 5 1 0 10 40 5 1 0 0 10 10 1 0 4 3 0...

Страница 45: ...ent flow Also accepts open collector solid state inputs sinking with maximum leakage current of 50 mA Start Stop Forward Reverse Configurable inputs for 2 or 3 wire control SW1 SW2 SW3 Configurable In...

Страница 46: ...o 25 seconds Overcurrent 200 hardware limit 300 instantaneous fault Excessive Temperature Embedded temperature sensor trips if heatsink temperature exceeds 95 C Over Under Voltage DC Bus voltage is mo...

Страница 47: ...cifications and Accessories A 4 For All Controller Ratings 0 37 to 2 2kW 1 2 to 3 HP Included with controller For Controller Ratings 0 37 to 2 2kW 1 2 to 3 HP The MTBF for the fan is 40 000 hours at 5...

Страница 48: ...he controller Use either DIN rail or mounting holes Use the drilling template at the back of the manual for mounting the controller D See Figure A 1 for details on controller dimensions and weights D...

Страница 49: ...A 6 Dimensions are shown in millimeters inches Dimensions are not to be used for manufacturing purposes 6 8 230 4 places 8 315 14 551 72 2 8 50 1 9 A B 7 5 295 86 4 3 4 29 1 1...

Страница 50: ...7 Dimensions are shown in millimeters inches Dimensions are not to be used for manufacturing purposes 40 2 1 6 71 2 8 5 1 199 Pin Extension 45 4 1 8 22 7 894 0 54 021 MOV MODULE L1 R L2 S L3 T A B E D...

Страница 51: ...eters inches Dimensions are not to be used for manufacturing purposes Important 3 Line Filter shown 1 Line Filter is the same size 60 2 36 6 236 5 197 130 5 11 152 5 98 163 6 41 50 1 97 200 7 87 Appro...

Страница 52: ...mensions are shown in millimeters inches Dimensions are not to be used for manufacturing purposes 110 9 4 37 150 9 5 94 254 10 Approximate Lead Length 40 1 5 50 1 97 4 5 177 Mounting Holes 140 5 51 13...

Страница 53: ...e shown in millimeters inches Dimensions are not to be used for manufacturing purposes 17 34 0 68 Required for Removal 161 2 6 35 Overall Height with DeviceNet Module 167 82 6 61 Overall Height with D...

Страница 54: ...Index I 1 4 1 4 1 1 0 3 1 3 3 1 1 1 1 0 0 3 3 3 0 4 3 1 3 1 2 3 1 3 1 3 0...

Страница 55: ...Index I 2 0 0 0 0 0 0 0 0 0...

Страница 56: ...Attach template to mounting surface and drill four 4 4 5 mm 0 177 inches diameter holes Dimensions are in millimeters inches...

Страница 57: ......

Страница 58: ......

Отзывы: