36
Rockwell Automation Publication 1500-UM055I-EN-P - December 2021
Chapter 2 Installation – Arc-Resistant Enclosure
Front Access – Access to Power Bus
1. Open the medium voltage power cell door (see
Figure 29 - ArcShield Power Cell (Upper)
2. Remove the 1/4-20 retaining screw (12 lb•ft [15N•m]) from the cable duct
barrier and remove the barrier (see
).
3. Remove the two 1/4-20 retaining screws (12 lb•ft [15N•m]) from the cable
duct boot and remove the boot (see
Figure 30 - Removing Cable Duct Boot and Barrier
ATTENTION:
To avoid shock hazards, lock out incoming power (see
Power Lock-out Procedure on page 53
) before working on the
equipment. Verify with a hot stick or appropriate voltage measuring
device that all circuits are voltage free. Failure to do so may result in
severe burns, injury or death.
Current Transformers
CT Mounting Plate
Loosen Retaining Screws
Cable Duct Boot
Remove Retaining Screws
Cable Duct Barrier