Locate and/or install single gang box.
Consult manufacturer’s instructions for installation.
2
Complete the wiring. Wire the cable to the control
module.
Wiring methods shall be in accordance with the National Electrical Code
(ANSI/NFPA70), CSA 22.1, Canadian Electrical Code (CEC), Part I, Safety
Standard for Electrical Installations, local code, and the authorities having
jurisdiction. A shielded cable must be used.
A power limited, class 2 UL 294 approved power supply must be used.
Voltage rating 5VDC to 28VDC.
Total length
to power supply or
to panel
Gauge to power supply
(power & ground wires)
Gauge to panel
(all other wires)
Power supply voltage
12 VDC
24 VDC
100 ft (30.5 m)
22
22
22
200 ft (61 m)
22
22
22
300 ft (91.5 m)
20
22
22
400 ft (121.9 m)
18
22
22
500 ft (152.4 m)
18
20
22
600 ft (182.9 m)
18
20
22
700 ft (213.4 m)
18
20
22
800 ft (243.8 m)
16
18
22
900 ft (274.32 m)
16
18
22
1000 ft (305.8 m)
-
18
22
Cable Connections
Black
Ground
Blue
Unused
Brown
Red LED Control
Gray*
Tamper Out
Green
Wiegand Data 0 / Data
Orange
Green LED Control
Pink
RS485-A/Y
Red
Power In
Shield
Shield Ground
Tan
RS485-B/Z
White
Wiegand Data 1 / Clock
Yellow
Beeper Control
Estimated Current Draw
MTB15
MTKB15
Input
Voltage
(VDC)
Avg. mA
Max. mA
Avg. mA
Max. mA
5
145
310
145
320
12
80
190
80
200
24
45
100
45
105
28
40
85
40
90
The max run for a 5V supply is 50 ft (15 m) with 18 AWG.
* Tamper Outputs are to be connected to a UL-Rated Burglary System.
3
Route cable through box.
Single Gang Reader
MTB15, MTKB15
Installation Instructions
Support and Warranty
us.allegion.com
(877) 671-7011
+1 512-712-1316
Allegion Address
3899 Hancock
Expressway
Security, CO 80911
Tools
• Phillips Screwdriver
• 6-32 Tap
• 1" (25 mm),
Z\,
" (3 mm) Drill Bits
• T10 Security Torx Screwdriver
(Optional)
For Indoor/Outdoor Use
MTB15
Mobile Enabled Multi-
Technology Reader
MTKB15
Mobile Enabled Multi-
Technology Reader with
keypad