TEST REPORT
Page
3
of
4
ANC 303
ALUMINIUM INDUSTRIES LIMITED
Relays Division
2.2
CURRENT UNBALANCE PROTECTION
Current unbalance
setting
Current Injected
Delay in ms
Observed Time in ms
2.5%
0.5A
20
40%
1A
100
80%
2A
500
Allowable tolerance limit is ±5%
2.3
SWITCH IN CURRENT
S/In setting
Current Injected
Delay in Sec
Observed Time in Sec
20% = 1.0A
1.01
1
30% = 1.5A
1.52
45
40% = 2A
2.02
70
Allowable tolerance limit is ±5%
2.4
SWITCH OUT CURRENT
S/Out setting
Current Injected
Delay in Sec
Observed Time in Sec
20% = 1.0A
0.90
60
30% = 1.5A
1.20
210
40% = 2A
1.5
360
Allowable tolerance limit in operating time is ±5%
2.5
TIME DELAY RELAY
TDR setting in min
TDR observed(Sec)
1
3
10
Allowable tolerance limit in operating time is ±5%
2.6
Local Breaker Backup (LBB) Trip
:Settings: OCR setting = 50%
LBB time setting
Current
Injected
Breaker status
LBB Status
LBB time (ms)
100ms
15A
Not operated
Operated
Operated
Not operated
500ms
10A
Not operated
Operated
Operated
Not operated
Allowable tolerance limit in operating time is ±5%
Содержание AN Series
Страница 3: ...Page 1 of 7 ANC 303 ALUMINIUM INDUSTRIES LIMITED Relays Division SAFETY REQUIREMENTS ...
Страница 10: ...Page 1 of 4 ANC 303 ALUMINIUM INDUSTRIES LIMITED Relays Division INTRODUCTION ...
Страница 14: ...Page 1 of 7 ANC 303 ALUMINIUM INDUSTRIES LIMITED Relays Division HANDLING INSTALLATIONS CASE DIMENSIONS ...
Страница 19: ...HANDLING INSTALLATIONS Page 6 of 7 ANC 303 CASE DIMENSIONS ALUMINIUM INDUSTRIES LIMITED Relays Division ...
Страница 20: ...HANDLING INSTALLATIONS Page 7 of 7 ANC 303 CASE DIMENSIONS ALUMINIUM INDUSTRIES LIMITED Relays Division ...
Страница 21: ...Page 1 of 16 ANC 303 THE ALUMINIUM INDUSTRIES LIMITED Relays Division USER GUIDE ...
Страница 27: ...USER GUIDE Page 7 of 16 ANC 303 ALUMINIUM INDUSTRIES LIMITED Relays Division BLOCK DIAGRAM ANC 303 ...
Страница 37: ...Page 1 of 7 ANC 303 ALUMINIUM INDUSTRIES LIMITED Relays Division TECHNICAL DATA CHARACTERISTIC CURVES ...
Страница 44: ...Page 1 of 4 ANC 303 ALUMINIUM INDUSTRIES LIMITED Relays Division TEST REPORT ...
Страница 48: ...Page 1 of 2 ANC 303 ALUMINIUM INDUSTRIES LIMITED Relays Division TROUBLESHOOTING ...