![Algas SDI Direct Fired F6-ASME Скачать руководство пользователя страница 17](http://html1.mh-extra.com/html/algas-sdi/direct-fired-f6-asme/direct-fired-f6-asme_operation-and-maintenance-manual_2896046017.webp)
Operation
Algas-SDI Operation and Maintenance Manual – P/N – 54000
6
CAUTION
The entire installation must be leak tested prior to operating the
system.
NOTE
Do not connect this vaporizer to a storage tank that has been used
in vapor withdrawal service until the tank has been emptied and all
sediment and heavy ends have been cleaned from it.
LIQUID INLET
NOTE
Do not install a check valve in the supply line between the tank and
the vaporizer. Liquid must be able to flow both ways in that line.
1. Ahead of the vaporizer inlet, install a 60-mesh strainer of equivalent size to
that of the vaporizer inlet connection.
2. Install a UL listed shut-off valve with a Minimum 250psi gas pressure rating
3. The liquid line from the storage tank to the vaporizer should be of sufficient
size to supply the vaporizer at full capacity with a maximum pressure drop of
less than the hydrostatic head pressure (
see
NFPA 54
).
4. Connect the vaporizer to the storage tank.
LIQUID SUPPLY LINE
(
see
Figure
3
)
The liquid supply line should be adequately sized for the service.
Table 2 – Recommended Liquid Supply Line Size (Nominal Pipe Size)
Liquid Line Length Ft. (m)
Up to 50 (15)
50-150 (15-36) 150-250 (36-76)
160H Vaporizers
1” (DN25)
1-1/4” (DN 32) 1-1/2” (DN40)
320H Vaporizers
1-1/4” (DN 32) 1-1/2” (DN40)
2” (DN50)
480H Vaporizers
1-1/4” (DN 32) 1-1/2” (DN40)
2” (DN50)
640H Vaporizers
2” (DN50)
2” (DN50)
2” (DN50)
800H Vaporizers
2” (DN50)
2” (DN50)
2” (DN50)
VAPOR DISTRIBUTION LINE
(
see Figure 3
)
The vapor distribution line should be adequately sized for the service.
Table 3 – Recommended Vapor Distribution Line Size (Nominal Pipe Size)
Gas Line Length Ft. (m)
Up to 50 (15)
50-150 (15-36) 150-250 (36-76)
160H Vaporizers
1-1/4” (DN 32) 1-1/2” (DN40)
2” (DN50)
320H Vaporizers
1-1/4” (DN 32) 1-1/2” (DN40)
2” (DN50)
480H Vaporizers
1-1/4” (DN 32) 1-1/2” (DN40)
2” (DN50)
640H Vaporizers
1-1/2” (DN40)
2” (DN50)
3” (DN80)
800H Vaporizers
1-1/2” (DN40)
2” (DN50)
3” (DN80)
Содержание Direct Fired F6-ASME
Страница 4: ...This page left intentionally blank...
Страница 7: ......
Страница 10: ...This page left intentionally blank...
Страница 35: ...Maintenance Algas SDI Operation and Maintenance Manual P N 54000 24 This page intentionally left blank...
Страница 41: ...Troubleshooting Algas SDI Operation and Maintenance Manual P N 54000 30 This page intentionally left blank...
Страница 42: ...APPENDIX A TECHNICAL INFORMATION...
Страница 43: ...Appendix A This page intentionally left blank...
Страница 50: ...Appendix A...
Страница 51: ...Appendix A...