18
The desired combustion power is selected via the P4 and P6 buttons. Press the P3 button to save the newly set value of
the parameter. To cancel all modifications and return to the old values, press the P1 button.
COMBUSTION RECIPE
Menu for selecting the combustion recipe. If only one recipe is set at the factory, this menu is not visible.
AUGER CALIBRATION
Menu for changing the feeding rate of the auger. The system has 10 calibration steps (from -5 to +5, the factory default is
0). The calibration effect is valid in the operating mode and in the modulation. For each step, the value is increased or decreased
by 5%.
Example: Calibration value = -2; (-2*5% = -10%) - means that the calibrated values of the auger speed will be reduced by
10% compared to the factory values.
Factory settings
C03=600
C04=900
C05=1200
C06=1600
C07=2000
C11=600
Calibrated values
C03=540
C04=810
C05=1080
C06=1440
C07=1800
C11=540
Combustion Fan Calibration
Menu for changing the number of revolutions of the flue gas fan. The system has 10 calibration steps (from -5 to +5; the
factory default is 0). The calibration effect is valid in the operating mode and in the modulation. For each step, the value is
increased or decreased by 5%.
Example: Calibration value = +3; (+3*5% = +15%) - means that the calibrated values of the fan speed of the flue gas fans
will be increased by 15% compared to the factory values.
Factory settings
U03=1000
U04=1200
U05=1400
U06=1600
U07=1800
U11=900
Calibrated values
U03=1150
U04=1380
U05=1610
U06=1840
U07=2070
U11=1030
Note: The calibration of the auger and flue gas fan must not be performed without prior consultation of an authorized
service or representative of the manufacturer.
15.3.2.
HEATING MANAGEMENT MENU
This is a menu for modifying parameters that determine the heating performance of the boiler. It contains several
submenus. The menu is accessed by pressing the P3 button and the following submenus appear:
Boiler Thermostat
A menu that allows you to adjust the set water temperature in the boiler. The temperature range of the water in the boiler
can be adjusted from 30°C to 80°C. By adjusting the set water temperature, the boiler will operate at the set power until it
reaches the set water temperature in the boiler. When the set water temperature is reached in the boiler, the boiler goes into
the state of modulation and continues to operate at minimum power.
Buffer Thermostat
Menu that allows the buffer temperature to be modified. This menu is only active if the buffer is installed.
Room Thermostat
In this menu, the set ambient probe temperature is modified. By pressing P4 and P6 buttons within Heating Management
menu we select Room Thermostat. The Room Thermostat menu is entered by pressing the P3 button.