15. STOVE STORAGE 

After  finishing  the  stoking  season,  the  stove  should  be  cleaned  from  ash  and  smoke.  Water  should  be 
released only in case when some repair of the installation should be performed. If the installation is not used 
in  the  heating  season,  pour  a  certain  quantity  of  some  antifreeze  liquid  or  release  the  water  from  the 
installation as a protection from freezing.   
 

16. FAULTS 

Table 3 

RB  Faults  

Possible cause 

Elimination  

Water pressure in 
installation is slowly 
decreasing 

The installation does not seal  

Check the sealing of welded 
connections, threaded fasteners, 
nuts etc. 

Cold radiators on the 
highest installation point 
and a sound is heard 

Air in the installation and low 
pressure in the installation 

Increase pressure in the installation 
and release air from the installation 
and from radiators 

The radiators do not 
heat along the entire 
length 

Air in radiators 

Release air from radiators through 
the vent valve 

The safety valve drains 
water from the 
installation, and the 
pressure is less than 3 
(2,5) bar 

Safety valve failure 

Replace safety valve 

The pressure in the 
installation is more than 
3 (2,5) bar and the 
safety valve does not 
drain water from the 
installation 

Safety valve failure 

Replace safety valve  

Sudden water 
temperate increase in 
the installation 

Air in the installation 

Perform radiator venting 

Closed valves towards radiators 

Open all valves in the heating 
system and provide normal water 
circulation in the installation 

Circulation pump failure 

The circulation pump should be 
repaired or replace it thereby 
allowing operation of the heating 
system 

Electrical power loss 

You should open all valves that 
reduced the heating system. This 
mostly refers to the “by-pass” 
valve. 
Stop or reduce stoking with strong 
control so that the water 
temperature in the system would 
not exceed 90

C until electricity 

arrives. 

Sudden pressure 
increase in the 
installation while water 
temperature increase 

Decreased pressure in the 
expansion vessel or completely 
empty. Remove the cover or the 
vessel valve cap and release some 
air through the valve. If the 
membrane is destroyed, water 
shall leak from the valve, and if it is 
only half-empty, only air will come 
out 

If water is leaking from the valve, 
replace the expansion vessel. 
If only air comes out from the 
valve, remove the installation 
vessel and pump it. The pressure 
in the vessel must be equal to or 
greater than height difference of 
the highest and lowest installation 
point. Example: 
For height difference of 5m. the 
pressure is Pmin.

0,5 bar. 

Содержание 20

Страница 1: ...1 STOVE FOR FLOOR HEATING ALFA TERM 20 INSTRUCTIONS FOR INSTALLATION ADJUSTMENT AND USE ...

Страница 2: ... mm Height min max 264 452 mm Depth 414 mm OPENING OF FIREBOX DOOR width height 175 200 mm CONNECTIONS OF DISCHARGE AND RETURN LINE R1 RS CONNECTIONS OF THERMO VALVE AND SAFETY VALVE R1 2 RU CONNECTIONS OF COOLING PIPES R1 2 RS BOILER VOLUME 14 l HEATING VOLUME WITH GRATE IN LOWER POSITION 280 380m3 total Heating volume of stove emission 100 135 m3 Heating volume of hot water radiators 180 230 m3 ...

Страница 3: ... The stove for floor heating is constructed so that it enables maximum safety during operation Safety during stove operation is provided in three ways combustion regulator thermostat fig 1 pos 10 located in the ashtray door which automatically closes the air intake in the stove firebox when the set water temperature in the boiler is reached Thermal valve thermal fuse Fig 7 Item 13 and Fig 7a when ...

Страница 4: ...4 1 2 18 7 16 17 13 11 25 12 3 4 5 6 15 14 19 20 21 22 7 8 16 17 10 11 9 23 24 9 Figure 1 ...

Страница 5: ...aches its rated power if the flue draft is 20Pa We recommend the following flue sizes with which this draft is obtained Stove Denotement Rated heating power kW Flue height m 6 7 8 9 10 ALFA TERM 20 Brown coal wood Dimensions of light surface mm 22 8 22 9 145x200 145x145 145x145 145x145 145x145 Proper flue and meeting other requirements set out in the material that follows are a prerequisite for fl...

Страница 6: ...erformed by a qualified person according to the appropriate project The stove is intended for floor and central heating It can be installed in closed and open heating system Adhere to the regulations JUS M E7 201 and JUS M E7 202 Diagrams of closed and open system are shown on fig 7 and fig 8 ...

Страница 7: ...ator with manometer 1 2 the same or similar as shown in Fig 7b and Fig 7 Item 19 3 Filter for cold water at the input of the water supply to the thermal valve Fig 7 Item 20 4 Filter for hot boiling water intake of the boiler and water outlet of thermal valve Fig 7 Item 21 Note These components are not included with product for central heating you bought Installation of thermal valve with built in ...

Страница 8: ...4 WATER FILTER OF THE BOILER OUTLET Fig 7 Item 21 It is required to install the filter on the boiler outlet which will clean the hot boiling water from dirt and solid objects that can damage the tap seals or seals of the thermal valve This filter must be resistant to water temperatures up to 150 C NOTES After the completion of thermal valve activation checking the pressure in the installation and ...

Страница 9: ...th pressure of 2 4 bar It is desirable that water is drained out from the system at least once because of the grime located in the system For an installation in which only a stove alfa term 20 is connected we recommend expansion vessel from 18 l but not less than 12 l which would be placed on returning water as close as possible to the boiler and no block valve should be set between the boiler and...

Страница 10: ...ressure regulator 20 Water filter at the input of the boiler 21 Water filter at the output of the boiler 22 Thermal fuse probe 23 Thermal fuse capillary pipe Figure 7a Figure 7b INSTALLATION DIAGRAM OF OPEN SYSTEM OF STOVE FOR FLOOR HEATING ALFA TERM 20 10 9 6 8 1 3 16 7 11 2 12 5 15 4 14 13 Figure 8 1 Hot water boiler 2 Flue extension 3 Distribution line 4 Open expansional vessel 5 Safety valve 6...

Страница 11: ...on which consumers radiators are connected with a minimum power of 8 kW When the system is cold the flap of the power regulator combustion regulator thermostat located in the ashtray door fig 1 pos 10 and pos 19 should be open Pull ahead the butterfly knob for opening and closing fig 1 pos 4 and fig 16 That way the butterfly knob is open and kindling is enabled Later when the stove is inflamed we ...

Страница 12: ...enters first and then put down the front part of the grate Move the grate forward and backward so that it lies well in the grate carrier bearing Put the hob in the carrier bearing of the hob frame Placement of the grate in lower position fig 9 and 10 is performed in the same manner as the upper position provided that in the end the front part of the grate is lifted a little and through the rectang...

Страница 13: ...irewood 15300 WARNING In order to get rated heating power and as higher rate of usage we recommend that you use dry beech wood cut with a length of L 33cm as a heating material 14 CLEANING AND MAINTENACE Before every filling with fuel the stove grate must be cleaned with a spade by opening the ember holders or through the open door of the firebox The ash from the ashtray should be removed at least...

Страница 14: ...rain water from the installation Safety valve failure Replace safety valve 6 Sudden water temperate increase in the installation Air in the installation Perform radiator venting Closed valves towards radiators Open all valves in the heating system and provide normal water circulation in the installation Circulation pump failure The circulation pump should be repaired or replace it thereby allowing...

Страница 15: ...Select low speed Air in installation Release air from the heating system Loose knobs or some screw on the stove Tighten knobs and screws 11 Sounds in the pump The pressure at the pump suction part is to low Increase system pressure or check the expansion vessel 12 The stove overheats loud noise cracking is heard in the boiler of the stove Electricity outage has occurred the circulation pump does n...

Страница 16: ...gh a thermostat or shortly open the ashtray door 18 There is too much heat in baking cooking The thermostat is set to a high temperature Reduce water temperature through the thermostat or stoke moderately 19 The boiler stove releases smoke during initial startup Combustion and heating of the stove and flue It is normal for the stove to release some smoke during initial startup and this stops after...

Страница 17: ...he guaranteed period with original spare parts for which we also provide a guarantee under the same conditions This guarantee does not exclude or affect the rights of the customer in regard to the conformity of the goods pursuant to the legal regulations If the delivered product does not conform to the agreement the customer has the right to ask the seller to repair that lack of conformity without...

Страница 18: ...18 Overall dimensions of stove ALFA TERM 20 300 309 712 781 797 806 64 152 268 5 64 235 1 1 1 2 RU 1 2 RU 1 2 RS 1 2 RS 880 850 100 500 1448 900 Ø146 Ø142 690 132 65 600 197 24 5 35 35 107 ...

Отзывы: