background image

 

11 

- It is desirable to insert a pump R1" for more speed whose flow capacity is always appropriate for the current 
need of the system. Directly in front and behind the pump, install shut-off valves so that displacement of the 
pump could be performed for repairs, changes etc., without releasing water.    
- Mount a tap for the filling and draining the system at the lowest system point. 
- Before commissioning the system should be filled with water as follows: 
  

a)  If  the  system  is  open,  fill  the  system  through  the  tap  for  filling  and  draining  until  water  starts  to  leak 

from the overflow pipe of the expansion vessel, 

b)  If the system is closed, the system pressure (working pressure) should be 1

1,5 bar. 

 
In both cases, fill the system slowly so that air can come out through the air releasing valves. If the valves do 
not open themselves, they should be manually open until water starts to leak, than close them. 
-  The  water  from  the  heating  system  should  not  be  drained  in  summer  neither  since  it  protects  the  internal 
side of the system from spreading oxidation (corrosion).  

If you don’t use the boiler for a longer period in winter, and there is not antifreeze asset in the system, it is 

best  to  drain  the  water  from  the  system.  At  the  same  time  open  the  valves  on  the  radiators,  the  combined 
valves and the other shut-off elements in the system. 
- Fire must not be kindled if the water in the boiler is frozen, neither if there is not enough water in the boiler. 
 

8. COMMISSIONING AND STOKING 

Before  stoking,  the  entire  system  for  floor  (central)  heating  should  be  filled  with  water,  well  vented  and  the 
stove should be properly connected to the flue as explained in the previous paragraphs.   

 
WARNING: 
The  stove  must  not  be  used  without  water.  It  must  be  connected  to  an  installation  on  which 
consumers (radiators) are connected with a minimum power of 8 kW. 

 
When  the  system  is  cold,  the  flap  of  the  power  regulator  (combustion  regulator,  thermostat)  located  in  the 
ashtray door (fig.1 pos.10 and pos.19) should be open. Pull ahead the butterfly knob for opening and closing 
(fig. 1 pos.4 and fig. 16). That way the butterfly knob is open and kindling is enabled. Later when the stove is 
inflamed, we adjust the regulator flap on the appropriate position that depends on the pulling power of the flue 
and the desired power, and the butterfly knob should be pushed back. Then the butterfly knob is closed and 
full  use  of  the  combustion  is  enabled,  thus  better  heating,  cooking  and  baking.  During  this,  the  door  of  the 
firebox  and  the  ashtray  (fig.  1  pos.  7  and  pos.  9)  must  be  closed  if  we  want  regulated  combustion.  The 
butterfly knob for kindling is open only during the kindling of the stove (10 to 15 minutes).  
The firebox and ashtray doors can be open and closed manually, as well as with the bent wrench as shown 
on figure 6. 
We stoke the stove as all permanently burning stoves on solid fuels. When the grade is in lower position, we 
perform kindling through the open door of the ashtray and the ember holder (fig.9 and fig.10). We open the 
ember holder (fig.1 pos.13 and fig.9) by raising and pulling. When the grate is in upper position through the 
open door of the firebox (fig.11) on the grate we put paper, small pieces of chopped wood and kindle. When 
everything is burning well, we can fill the stove with wood or coal if the grate is in upper position. If the grate is 
in  lower  position,  do  not  put  at  once  all  the  needed  heating  material  for  full  firebox,  but  divide  it  on  two  or 
three parts and put it in the firebox at intervals of 10-15 minutes on flaming heating material. The stove filled 
in  this  manner  burns  from  1  to  6  hours,  depending  on  the  intensity  of  combustion  in  the  stove  and  the 
adjusted power regulator (thermostat).  
 

 

Figure 9  

 

 

    Figure10 

                  Figure 11 

 

Содержание 20

Страница 1: ...1 STOVE FOR FLOOR HEATING ALFA TERM 20 INSTRUCTIONS FOR INSTALLATION ADJUSTMENT AND USE ...

Страница 2: ... mm Height min max 264 452 mm Depth 414 mm OPENING OF FIREBOX DOOR width height 175 200 mm CONNECTIONS OF DISCHARGE AND RETURN LINE R1 RS CONNECTIONS OF THERMO VALVE AND SAFETY VALVE R1 2 RU CONNECTIONS OF COOLING PIPES R1 2 RS BOILER VOLUME 14 l HEATING VOLUME WITH GRATE IN LOWER POSITION 280 380m3 total Heating volume of stove emission 100 135 m3 Heating volume of hot water radiators 180 230 m3 ...

Страница 3: ... The stove for floor heating is constructed so that it enables maximum safety during operation Safety during stove operation is provided in three ways combustion regulator thermostat fig 1 pos 10 located in the ashtray door which automatically closes the air intake in the stove firebox when the set water temperature in the boiler is reached Thermal valve thermal fuse Fig 7 Item 13 and Fig 7a when ...

Страница 4: ...4 1 2 18 7 16 17 13 11 25 12 3 4 5 6 15 14 19 20 21 22 7 8 16 17 10 11 9 23 24 9 Figure 1 ...

Страница 5: ...aches its rated power if the flue draft is 20Pa We recommend the following flue sizes with which this draft is obtained Stove Denotement Rated heating power kW Flue height m 6 7 8 9 10 ALFA TERM 20 Brown coal wood Dimensions of light surface mm 22 8 22 9 145x200 145x145 145x145 145x145 145x145 Proper flue and meeting other requirements set out in the material that follows are a prerequisite for fl...

Страница 6: ...erformed by a qualified person according to the appropriate project The stove is intended for floor and central heating It can be installed in closed and open heating system Adhere to the regulations JUS M E7 201 and JUS M E7 202 Diagrams of closed and open system are shown on fig 7 and fig 8 ...

Страница 7: ...ator with manometer 1 2 the same or similar as shown in Fig 7b and Fig 7 Item 19 3 Filter for cold water at the input of the water supply to the thermal valve Fig 7 Item 20 4 Filter for hot boiling water intake of the boiler and water outlet of thermal valve Fig 7 Item 21 Note These components are not included with product for central heating you bought Installation of thermal valve with built in ...

Страница 8: ...4 WATER FILTER OF THE BOILER OUTLET Fig 7 Item 21 It is required to install the filter on the boiler outlet which will clean the hot boiling water from dirt and solid objects that can damage the tap seals or seals of the thermal valve This filter must be resistant to water temperatures up to 150 C NOTES After the completion of thermal valve activation checking the pressure in the installation and ...

Страница 9: ...th pressure of 2 4 bar It is desirable that water is drained out from the system at least once because of the grime located in the system For an installation in which only a stove alfa term 20 is connected we recommend expansion vessel from 18 l but not less than 12 l which would be placed on returning water as close as possible to the boiler and no block valve should be set between the boiler and...

Страница 10: ...ressure regulator 20 Water filter at the input of the boiler 21 Water filter at the output of the boiler 22 Thermal fuse probe 23 Thermal fuse capillary pipe Figure 7a Figure 7b INSTALLATION DIAGRAM OF OPEN SYSTEM OF STOVE FOR FLOOR HEATING ALFA TERM 20 10 9 6 8 1 3 16 7 11 2 12 5 15 4 14 13 Figure 8 1 Hot water boiler 2 Flue extension 3 Distribution line 4 Open expansional vessel 5 Safety valve 6...

Страница 11: ...on which consumers radiators are connected with a minimum power of 8 kW When the system is cold the flap of the power regulator combustion regulator thermostat located in the ashtray door fig 1 pos 10 and pos 19 should be open Pull ahead the butterfly knob for opening and closing fig 1 pos 4 and fig 16 That way the butterfly knob is open and kindling is enabled Later when the stove is inflamed we ...

Страница 12: ...enters first and then put down the front part of the grate Move the grate forward and backward so that it lies well in the grate carrier bearing Put the hob in the carrier bearing of the hob frame Placement of the grate in lower position fig 9 and 10 is performed in the same manner as the upper position provided that in the end the front part of the grate is lifted a little and through the rectang...

Страница 13: ...irewood 15300 WARNING In order to get rated heating power and as higher rate of usage we recommend that you use dry beech wood cut with a length of L 33cm as a heating material 14 CLEANING AND MAINTENACE Before every filling with fuel the stove grate must be cleaned with a spade by opening the ember holders or through the open door of the firebox The ash from the ashtray should be removed at least...

Страница 14: ...rain water from the installation Safety valve failure Replace safety valve 6 Sudden water temperate increase in the installation Air in the installation Perform radiator venting Closed valves towards radiators Open all valves in the heating system and provide normal water circulation in the installation Circulation pump failure The circulation pump should be repaired or replace it thereby allowing...

Страница 15: ...Select low speed Air in installation Release air from the heating system Loose knobs or some screw on the stove Tighten knobs and screws 11 Sounds in the pump The pressure at the pump suction part is to low Increase system pressure or check the expansion vessel 12 The stove overheats loud noise cracking is heard in the boiler of the stove Electricity outage has occurred the circulation pump does n...

Страница 16: ...gh a thermostat or shortly open the ashtray door 18 There is too much heat in baking cooking The thermostat is set to a high temperature Reduce water temperature through the thermostat or stoke moderately 19 The boiler stove releases smoke during initial startup Combustion and heating of the stove and flue It is normal for the stove to release some smoke during initial startup and this stops after...

Страница 17: ...he guaranteed period with original spare parts for which we also provide a guarantee under the same conditions This guarantee does not exclude or affect the rights of the customer in regard to the conformity of the goods pursuant to the legal regulations If the delivered product does not conform to the agreement the customer has the right to ask the seller to repair that lack of conformity without...

Страница 18: ...18 Overall dimensions of stove ALFA TERM 20 300 309 712 781 797 806 64 152 268 5 64 235 1 1 1 2 RU 1 2 RU 1 2 RS 1 2 RS 880 850 100 500 1448 900 Ø146 Ø142 690 132 65 600 197 24 5 35 35 107 ...

Отзывы: