6.4  Refrigerant connections

Do not adapt headers position to the suction line.

All pipework and connections must be made in accordance with good refrigeration design and

installation practice. Ensure that no stresses are transmitted to the pipework. All pipework should be

adequately attached to the walls/ceilings of the cold room and not only to the cooler itself. Pipework

must be adequately supported to prevent vibration or external load on the cooler headers, etc. 

Ensure the supply circuit is closed (no pressure) 

before connecting the suction lines. 

Ensure the flame nozzle is not aimed at the 

equipment, when welding. Insert a protection 

shield if required.

Содержание LU-VE Optigo FMS25

Страница 1: ...ORIGINAL INSTRUCTIONS 31592031EN 01 Optigo FMS Instruction manual Product description Product labels Unpacking lifting Installation Maintenance Spare parts FMS25 FMS30...

Страница 2: ...nal features 5 2 4 Code description 6 3 Product labels 6 4 Transport and storage 8 5 Unpacking and lifting 8 6 Installation 10 6 1 Mounting dimensions 10 6 2 Mounting bracket 11 6 3 Technical spaces 1...

Страница 3: ...dividual product models are available in order related documents on the product label and in product data sheets Comprehensive technical information for all Alfa LU VE air heat exchanger products is a...

Страница 4: ...ry At the moment of delivery carefully check the units All finned coils are pressure tested with dry air sealed and supplied with a slight overpressure Prior to installation the leak resistance must b...

Страница 5: ...2 according to EN 378 2 2 Standard configuration High efficiency coil manufactured from internally grooved Cu tubes and aluminium fins Optigo FMS coolers are available with 1 to 4 fans Fitted with AC...

Страница 6: ...AL aluminium AP pre painted aluminium 10 Packing BO box BP box pallet CR crate 3 Product labels Manufactured by SEST LUVE POLSKA sp z o o ul Wycz lkowskiego 30 44 109 Gliwice Poland HEAT EXCHANGER FMS...

Страница 7: ...P L E 1 Product label This label is positioned inside the casing Model Refer to paragraph 2 4 Code description Product code Product Serial nr Communicate these when ordering spare parts as they ident...

Страница 8: ...packing in a dry place with sufficient protection against sun and other environmental influences Always place air heat exchangers on an even surface Do not stack air heat exchangers unless explicitly...

Страница 9: ...o the driptray or the finned coil Utilizing the proper wooden transport beams and or pallets prevents the cooler bending at the extremes such that the cooling circuit or other components are damaged L...

Страница 10: ...er expansion occurs during defrost For air coolers with copper tubing this figure runs up to 1 65 mm per meter cooler length All heat exchangers must be set up level Weight information are listed on t...

Страница 11: ...et side of the heat exchanger The air discharge side should be free of restrictions Recirculation of air is to be avoided The heat exchangers should not be connected to ducting on either the air inlet...

Страница 12: ...ccordance with good refrigeration design and installation practice Ensure that no stresses are transmitted to the pipework All pipework should be adequately attached to the walls ceilings of the cold...

Страница 13: ...alve fitted must be correctly sized for the installation conditions and adjusted for correct system operation 6 5 Pressure test 6 6 Drain line Check all drain lines and driptrays to ensure that no imp...

Страница 14: ...re designed for TN power systems The insulation fault protection must be part of power supply of the heat exchanger and is not supplied by the manufacturer The following data determine which connectio...

Страница 15: ...or power consumption n of fans 1 2 3 4 AC 1 230 V 50 60 Hz 254 62 W 0 4 A 124 W 0 8 A AC 1 230 V 50 Hz 300 70 W 0 32 A 140 W 0 64 A 210 W 0 96 A 280 W 1 28 A AC 1 230 V 60 Hz 300 95 W 0 42 A 190 W 0 8...

Страница 16: ...h trial and error according to the actual defrost requirements depending on cooler model size and working conditions If the defrosting cycle is terminated via a temperature sensor close attention must...

Страница 17: ...hout prior notification FMS30 Model No fans Coil type E no W connection scheme FMS30 1 1 1 740 A FMS30 1 2 1 1130 B FMS30 1 3 1 1200 A FMS30 1 4 1 1755 B FMS30 2 1 1 1400 A FMS30 2 2 1 2130 B FMS30 3...

Страница 18: ...to change specifications without prior notification 6 12 Driptray heater HD FMS30 Model No fans Coil type HD no W FMS30 1 1 1 200 FMS30 1 2 1 200 FMS30 1 3 1 315 FMS30 1 4 1 315 FMS30 2 1 1 385 FMS30...

Страница 19: ...n operation A lesser known problem is that small amounts of moisture in the refrigeration system can after a time cause leakage through the formation of frost clumps These frost clumps are the result...

Страница 20: ...e handling heater elements always disconnect power supply ensure heaters are at ambient temperature E driptray P P Disconnect drain line Open the driptray and side covers on both sides Open side cover...

Страница 21: ...Fan blades should also be checked for any erosion or corrosion and remedial action taken as necessary All dirt and other contamination should be removed to avoid imbalanced running of the fan and mot...

Страница 22: ...ot Use reliable protection Working fluids Working fluids might be toxic and or flammable These substances may only be handled by qualified staff while taking all necessary precautions and following an...

Страница 23: ...ions without prior notification 10 Spare parts Spare parts Optigo FMS25 1 Fan guard 2 Fan impeller 3 Fan motor 4 Electrical defrost E Spare parts Optigo FMS30 1 Fan guard 2 Fan impeller 3 Fan motor 4...

Страница 24: ...alfa luvegroup com...

Отзывы: