36
Effective 05/04/2012
Unique PMO Plus CP HT Valve Series
Series Sanitary Mixproof Valve Instruction Manual
Valve Seat Position Indication
Test - 2
Lower Valve Seat
Position Detection
AC3
On Off
'A' LED
(Closed Valve)
1. Valve at rest (closed) position
· "A" LED (Closed Valve) on
Think
Top is illuminated.
2. Attach a manual air line to actuator air fitting AC3 using a
3-way air pilot switch (pos. 102).
3. Turn the air pilot switch to ON (Open)
· "A" LED (Closed Valve) on
Think
Top not illuminated.
4. Turn the air pilot switch to Off (Closed).
· "A" LED (Closed Valve) on
Think
Top is illuminated.
5. Test complete. Remove manual air line.
102
See pages 66 to 74 for part numbers.