Alfa Laval AquaFirst
Installation, service and operating instruction
28
7.11 Autotest menu
Accessing the Autotest menu requires login at Technician level.
This submenu allows testing analog (contacts) and digital (0-10V) outputs that manage pumps start/stop, both
programmable relays, 23
0V Triac output and valve’ signal. It is possible to run an automatic sequence or to test
manually each output individually.
In case of Auto test (automatic sequence), it is possible to reduce or increase tests’ temporizations. Pump,
valve and relays test times can be adjusted individually. The time test value will impact on the total auto test
time sequence.
Parameter
Factory
Setting
Optional Setting
Description
Start AutoTest
0
0/1
Set 1 to start auto test. When finished, the value
goes back to zero.
Pump_Fault_Reset
Off
Off/On
Set to On after an Auto test.
Pump time test
4 sec
1-600 sec
Not used
Valve time test
4 sec
1-600 sec
Temporisations to adjust test duration.
Alarm time test
4 sec
1-600 sec
Relays 1 and 2 test
Cmd_P1
On/Off
On/Off
Activates pump 1 relay
Cmd_P2
Off/On
On/Off
Activates pump 2 relay
Speed_P1P2
xx %
0-100 %
Not used
Cmd_P3
On/Off
On/Off
Activates pump 3 relay
Cmd_P4
Off/On
On/Off
Activates pump 4 relay
Speed_P3P4
xx %
0-100 %
Not used
Relay 2
Off
On/Off
Activates relay 2
Relay 1
Off
On/Off
Activates Relay 1
Triac_Output
Off
On/Off
Activates 230V triac output
Valve signal
xx %
0-100 %
Valve opening/closing
Valve2 signal
xx %
0-100 %
N/A
Valve_DO
xx %
0-100 %
N/A