Subject
Page
OPERATING INSTRUCTIONS
30
of
38
www.alfalaval.com
7.3.7
Self draining
If for some reason, active draining with pump is not applicable, it is possible
to self-drain the system with gravity only.
Open V01-V05 valves on the CIP unit.
Connect the drain of the CIP tank/tanks to a suitable barrel.
Open the valve V07 on the tank together with drain valve V06 (and V14 for CIP
400L-see P & I diagram) and drain the unit completely.
Close all valves after the draining.
7.3.8
Self draining of the heat exchanger only
Close all valves.
At the CIP unit, disconnect the hose that is fitted to the lower connection on the
heat exchanger. Be careful since CIP liquid might escape from hose end.
Place the end of the hose in a barrel or other collection vessel.
Open valve V05 and V02 to let air in.
Drain the heat exchanger