ALENCON GARD-1000-V2.2 Скачать руководство пользователя страница 15

GARD – Installation, Operation and Maintenance Manual

 

 

              

A l e n c o n   S y s t e m s   L L C   -   P a g e

 | 14 

4.4  GARD Functionality and Operation 

  Functionality 

The  SPOT  or  any  upstream  equipment  is  connected  to  the  PV  System  via  the  GARD.  The 
communication with GFDI/AFD is carried out via MODBUS.   
 
The  GFDI provide ground and arc fault protection features to the existing SPOTs.  The GARD 
generates its own control voltages. A microcontroller monitors the currents and voltages in all four 
PV  channels and  controls and monitors the AFD module. Self-tests on the GFDI and  AFD are 
performed automatically every day.  
 
In  the  event  of  a  fault,  the  faulty  channel  is disconnected  preventing  ground  leakages  and  arc 
flashes on the commensurate input PV wires. Local indicators report the status of the GARD. A 
remote monitoring facility is available via MODBUS.  The operator can enforce the disconnection 
manually  by  using  an  external  switch  (E-STOP)  or  remotely  by  sending  MODBUS  commands. 
After the system is safely shutdown and the fault cleared, the GARD can be manually reset using 
the reset push button available locally on the GARD or via a Modbus Reset command. 

  Instructions when Ground Fault is Detected 

In the event of a ground fault, the faulty channel is disconnected preventing ground currents from 
flowing. Local indicators report the status of the GARD. A remote monitoring facility is available 
via MODBUS. Follow the suggested actions below; 
 

1.  When a ground fault is indicated the corresponding channel will trip and indicate a ground 

fault. The ground current will be interrupted by the GARD. When the unit is tripped the LED 
for  the  tripped  channel  on  the  GARD  will  turn  RED.  The  status  of  the  GARD  can  be 
monitored on the HUB user interface. Refer to the HUB manual for more information. 

2.  When a ground fault is indicated normally grounded conductors may be ungrounded and 

energized or normally ungrounded conductors may be grounded. 

3.  The ground fault will be on the channel that tripped due to ground fault. 
4.  Press E-Stop button to disconnect all other channels. 
5.  Check the input and output wires of the tripped channel to make sure there is no current 

flowing. 

6.  After  ensuring  that  there  is  no  current  flowing  through  the  tripped  GARD  channel, 

disconnect the input and the output wires. 

7.  Once the tripped channel is safely disconnected, reset the GARD by disengaging the E-

STOP button and pushing the Reset switch. The GARD can also be reset using the HUB 
user interface. 

8.  Disconnected PV strings must be inspected by the authorized maintenance personnel. 
9.  Once the faulty string(s) are restored they can be reconnected back to the GARD channel. 

 

Содержание GARD-1000-V2.2

Страница 1: ...d and arc faults in PV arrays and rapidly disconnecting the impacted PV strings INSTALLATION OPERATION AND MAINTENANCE MANUAL FOR USE WITH THE GARD V2 2 PM006 Revision 7 Alencon Systems LLC 330 Warmin...

Страница 2: ...ems LLC and or organization names mentioned may be trademarks and or registered trademarks of their respective companies Publication Number PM006 Date and Revision Revision ECO Date Author Approval Co...

Страница 3: ...Arc Faults in Your PV Array 12 4 1 The Ground Arc Rapid Disconnect Unit GARD 12 4 2 Unique Features Benefits of the Alencon GARD 12 4 3 GARD Specifications 13 4 4 GARD Functionality and Operation 14...

Страница 4: ...IRECT CURRENT SUPPLY 8 FIGURE 4 GROUNDING SCHEMES 10 FIGURE 5 ARCING 11 FIGURE 6 AFD PCB 16 FIGURE 7 SYSTEM NOISE SIGNATURE DURING AN ARC EVENT 17 FIGURE 8 PV SPOT INVERTER SYSTEM NOISE SIGNATURE 17 F...

Страница 5: ...the Alencon s Ground Rapid Disconnect Unit Who Should Read this Manual This manual should be read by anyone who needs to Understand the product Plan the installation Install the product Commission th...

Страница 6: ...ystems high quality control standards and rigorous testing most of our customers never need to use our warranty service If an Alencon Systems product is defective it will be repaired or replaced at no...

Страница 7: ...r technical support if you need additional assistance Please have the following information ready before you call Product name LIN and serial number see section 6 5 for more information the location o...

Страница 8: ...Before installation please ensure the following items have been shipped Correct of GARD Units specified for your plant with appropriate mounting hardware Figure 1 The GARD Unit 1 7 Ordering Informati...

Страница 9: ...anada 1 Before installing and using the GARD read all instructions presented in this manual and the cautionary markings shown on the GARD s enclosure 2 The GARD contains no user serviceable parts For...

Страница 10: ...ly Ignoring to do so may result in a risk of fire 8 PV modules produce electrical energy when exposed to light and thus can create an electrical shock hazard Wiring of the PV modules should only be pe...

Страница 11: ...e terminals are connected to a conductive load the current begins to flow from the source to the load thereby generating power Figure 4 Grounding schemes A ground fault is an inadvertent contact betwe...

Страница 12: ...of the SPOT Should you wish to positively ground the system this should be indicated prior to order As the GARD is designed for use with the SPOT the grounding of the PV array will appear as floating...

Страница 13: ...with either a local or global E STOP switch or via remote MODBUS commands The GARD can be deployed as a standalone device or in conjunction with Alencon s String Power Optimizer and Transmitter the S...

Страница 14: ...tors Yes Ground Fault Detector Capabilities Common grounding Negative Positive Ground fault current trip levels Configurable from 500 mA to 1 A Overvoltage Class OV II ARC Fault Detector Capabilities...

Страница 15: ...he faulty channel is disconnected preventing ground currents from flowing Local indicators report the status of the GARD A remote monitoring facility is available via MODBUS Follow the suggested actio...

Страница 16: ...of the tripped channel to make sure there is no current flowing 7 After ensuring that there is no current flowing through the tripped GARD channel disconnect the input and the output wires 8 Once the...

Страница 17: ...ing a RESET command via MODBUS RTU GFDI can be configured to detect a ground leak either for negatively grounded positively grounded or floating PV systems 4 4 4 4 Arc Detection The arc fault detector...

Страница 18: ...peration of a PV system the noise floor fluctuates depending on operating conditions transient s etc Alencon s AFD is conctantly monitoring the noise floor for deviations in spectrum magnitude During...

Страница 19: ...e PCB motherboard and one daughter PCB The motherboard provides the following functions Controls Ground Leak Fault Detection Arc Detection Board PV Disconnect upon fault Channel Status The Motherboard...

Страница 20: ...negative current sensor This difference should simulate a current fault If any of the channels fail to detect the simulated fault they will be disconnected and a fault flag will be recorded in the GA...

Страница 21: ...tate and keeps all relays de energized as long the SHUTDOWN flag is set TESTMODE Upon receiving the TESTMODE command the GARD AFD is initialized and initially set into SHUTDOWN state While in TESTMODE...

Страница 22: ...would have to push the button in towards the GARD This will put the switch in the NO position disconnecting the power to the relays To disengage the emergency switch twist and pull the knob away from...

Страница 23: ...work Through the same RJ45 connector all the GARDs in the network are wired to a global E STOP that can remotely disable the GARD i e disconnect isolate PV strings from the Output Figure 12 GARD Botto...

Страница 24: ...lat installation where the E Stop botton faces upward No cooling is required for the GARD When mounting the GARD 1 Have at least 2 feet of clearance from the ground Installing the GARD at chest height...

Страница 25: ...Manual A l e n c o n S y s t e m s L L C P a g e 24 Figure 14 GARD prior to mounting on the Unistrut 7 4 Cable Terminations The GARD can either be used as a standalone product in a PV system or couple...

Страница 26: ...GARD SPOT If the PV system is already fitted with SPOT s you must be pay attention to the physical connectors that go from the GARD to the SPOT To break it down the list below explains how input outp...

Страница 27: ...used to de energize the PCS or other power conversion equipments connected to its output terminals External disconnects are not required however the PV strings must be fused in order to comply with th...

Страница 28: ...tup applying minimum voltage or external 24 V will turn ON the GARD boards allowing two way communications with the HUB 8 2 Control System All protection tasks controls and communication are handled b...

Отзывы: