UXBM Harness and Tab Washer Installation
4200-088
9-13
Revision 1.03
The following is an example connection for a 4 x 12V split power load scenario on a string.
Figure 18 - Power Connection for UXBM Monitoring with a Split Load of 4 x 12V
The following table will illustrate recommended minimum cells or monoblocs required to power the
UXBM.
Cell/Monobloc nominal unit voltage
Minimum amount of units to be included within the
power connections at worst case 1.65V end voltage
2V
5
4V
3
6V
2
8V
2
12V
1
16V
1
Table 5 - Recommended Power Lead Connection