CFP USER MANUAL • Approved Document No. DFU7001020 Rev 1 • Page 7 of 20
CFP 2/4/8 ZONE CONVENTIONAL FIRE ALARM PANEL
LIGHT
STATUS OF LIGHT
WHAT THIS MEANS
FURTHER READING
(General Fire)
Flashing Red
The panel has detected a fire alarm condition, or
the Silence/Resound Sounders button has been
pressed to evacuate the building
Page 8 (Fire Conditions)
Steady Red
There is a silenced fire alarm condition on the
system
Fire Zones
1 to 8
Flashing Red
A fire alarm condition has been detected on the
zones which are flashing
Steady Red
There is a silenced fire alarm condition on the
zones which are lit steady
Zone Fault/Disable/Test
1 to 8
Flashing Yellow
(in sync. with the
General Fault light)
Faulty wiring has been detected on the zones
which are flashing
Page 9 (Fault Conditions)
Flashing Yellow
(in sync. with the
Test light)
The zones which are flashing are in test mode
Steady Yellow
The zones which are lit steady have been disabled Page 10 (Disablements)
Supply Present
Steady Green
The panel is supplied with power
Page 4 (Overview)
Remote Output
Steady Red
The remote output has been activated
Test
Flashing Yellow
The panel is in test mode
Accessed
Flashing Yellow
The access code is in the process of being entered Page 6 (Accessing the Controls)
Steady Yellow
The panel is in access level two
General Disablement
Flashing Yellow
The panel is in the disablement selection state
Page 10 (Disablements)
Steady Yellow
Part of the system has been manually disabled
and/or one or more of the fire zones have a delay
applied to them (CFP model dependent - see page 3)
Page 10 (Disablements)
Page 12 (Notes on Delays)
Fault Output Status
Steady Yellow
The fault output has been disabled
Page 10 (Disablements)
Remote Output Status
Flashing Yellow
A fault has been detected on the output’s auxiliary
24V supply
Page 9 (Fault Conditions)
Steady Yellow
The remote output has been disabled
Page 10 (Disablements)
General Fault
Flashing Yellow
A fault has been detected on the system
Page 9 (Fault Conditions)
Power Supply Fault
Flashing Yellow
The panel has detected a fault with its power
supply, battery charger or back-up batteries
System Fault
Flashing Yellow
The panel has detected a microprocessor fault
Repeater Fault (model
dependent - see page 3)
Flashing Yellow
The panel has detected a wiring/communication
fault on the repeater network
Sounder Status
Flashing Yellow
Faulty wiring has been detected on the panel’s
sounder circuits
Steady Yellow
The alarm sounders have been disabled
Page 10 (Disablements)
Auxiliary Output Status
Steady Yellow
The panel’s auxiliary output has been disabled
Page 10 (Disablements)
Output Delays (CFP
model dependent - see
page 3)
Steady Yellow
Delays have been programmed into the panel
Page 12 (Notes on Delays)
Flashing Yellow
A delay is running
What the indicator lights mean
The table below summarises the various indicators available on the fire alarm panel and what they mean in their
various states. The final column highlights the pages(s) you should turn to for further information.
Testing the indicator lights
To test the panel’s indicator lights are working correctly, press the Lamp Test button when the panel is in the
accessed state. The panel’s internal beeper also sounds when pressing this button to show it is working correctly.
FIRE