3.2 Terminal Descriptions
All terminal strips are removable with locking screws and accept wire sizes from 12-26AWG. Wire
should be sized appropriately for voltage drop and current carrying capability. All terminals are
labelled for polarity or phasing where appropriate.
Figure 3.2.1
C
NC
NO
AC
FAULT
COMMON
FAULT
C
NC
NO
-
+
24V
DC
12V
DC
BAT
+
-
+
-
DC Power Supply
Configure internal jumpers prior to use
See Instruction Manual 52-XXX
OUT8
OUT7
OUT6
OUT5
OUT4
OUT3
OUT2
OUT1
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
Remove load or reset main power to restore PTC protected zones
For fused units remove front panel to replace fuse.
On other than ‘F’ series units, OUT1 thru OUT8 are Class 2 Power Limited
AC POWER
OFF
RESET
ON
Rear Panel
OUT32 OUT31 OUT30 OUT29
OUT28 OUT27 OUT26 OUT25
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
Remove load or reset main power to restore PTC protected zones
For fused units remove front panel to replace fuse.
On other than ‘F’ series units, OUT17 thru OUT32 are Class 2 Power Limited
OUT24 OUT23 OUT22 OUT21
OUT20 OUT19 OUT18 OUT17
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
AC Power Supply
Configure internal jumpers prior to use
See Instruction Manual 52-XXX
12V
BULK
OUTPUT
24V
BULK
OUTPUT
BATTERY
CONNECT
AC FAULT
OUTPUT
COMMON
FAULT OUTPUT
DC
DISTRIBUTED
OUTPUTS
AC
DISTRIBUTED
OUTPUTS
3.2.1 AC Input
120 VAC Input: cord set - AlarmSaf Part# A095057
3.2.2 Distributed DC Outputs (Out1 - Out8)
Each distributed output is individually over-current protected (3A for fuse protected units,
1.6A for PTC protected units). Each output can be programmed for voltage by front panel
jumper selection.
3.2.3 Battery Terminals (BAT +/-)
Product uses 24V battery set to provide backup to both 12VDC and 24VDC outputs
Battery only provides backup to the DC portion of the supply
Terminals internally fused at 15 Amps
Battery presence detection available by setting internal jumpers
Minimum battery charging capacity: 7 Amphours
Maximum battery charging capacity: 80 Amphours within 48 hours
Contact AlarmSaf for spreadsheet-based battery software, PowerCAD 2.0
Note -
It is the responsibility of the installer to determine the minimum battery requirement for the
particular application in which the supply is being used. Backup batteries should be serviced at
regular intervals as determined by local and/or national codes.
3.2.4 Bulk 24V Output Terminals (24VDC +/-)
Bulk 24V output of internal supply. Full current capacity of supply is available on this single
output terminal set.
3.2.5 Bulk 12V Output Terminals (12VDC +/-)
Bulk 12V output of internal supply. Full current capacity of supply is available on this single
output terminal set.