4.2 Wiring

4.2.1 Wire Routing

All wiring must be installed in accordance with NFPA70  [NEC760] and all local code
requirements.

Power Limited wiring requires that power limited and nonpower limited wiring remain physically
separated. All power limited circuits must remain at least one quarter inch (¼") away from any
nonpower limited circuit wiring.

CAUTION - A lead-acid or gel cell battery can supply large amounts of current.  Although
the RMBE has limiters on each battery, care should still be taken when wiring the  RMBE to
prevent personal or property damage.  Always remove the terminal st rips when wiring an
RMBE and ensure proper wiring before reconnection of the terminal strips.

Figure 4.2.1

12V

24V

Battery Set 2 Configuration

OR

IN-Parallel Set 1 and 2

OUT-Separates Set 1 and 2

BATTERY

CONNECT

+ - + -

The RMBE contains 2 battery sets which may be configured for:
12V / 12V - Two separate outputs; 24V / 24V Two separate outputs
12V and 24V - Two separate outputs
12V - One single output or 24V - One single output

VOLTAGE SELECTION

4.2.2 Battery Connection

Locate the terminal wiring blocks on the back panel of the unit and remove the terminal block
from the header (there are two locking screws, one on either end of the terminal block).  Connect
the wiring to the terminal block.  The back panel of the enclosure is labeled with the terminal and
polarity indications (See also Section 3.2).  Replace the terminal block on the header and tighten
the locking screws.

NOTE - When the “Parallel Set 1 and 2” jumper is in place, both output terminal strips are
paralleled into a single battery set, and either terminal strip may be used.

4.2.3 Paralleling RMBE Enclosures for Increased AH capacity

Each battery set’s terminal strip has two separate pairs of output terminals.  The extra pair of
terminals can be used to connect to an additional RMBE unit for increased amphour capacity.
Ensure correct polarity of wiring and correct setting of the configuration jumpers on 

ALL

 RMBE

enclosures before connecting two or more RMBE enclosures together.

Rack Mount Battery Enclosure Installation Instructions
5/27/2009, 11:42:41 AM

52-342 Rev A.01

Page 9 of 14

AlarmSaf

 65A Industrial Way, Wilmington, MA 01887 978 658 6717 www.alarmsaf.com

Содержание RMBE Series

Страница 1: ...RMBE Series Rack Mount Battery Enclosure Operating and Installation Instructions 52 342 Rev A 01...

Страница 2: ...working about the premesis by falling objects by customers by building vibration and by similar causes NOTICE This equipment is not intended for use within the patient care areas of a Health Care Faci...

Страница 3: ...the RMBE Series 9 4 2 Wiring 7 4 1 Mounting 7 4 Installation 6 3 2 Terminal Descriptions 5 3 1 Electrical Ratings and Specifications 5 3 System Overview 5 2 Applicable Standards Documents 4 1 Introduc...

Страница 4: ...es total of four 7AH batteries Each individual battery is protected by an internal self resetting PTC Each battery set can be configured for either 12VDC or 24VDC When set for the same voltage the two...

Страница 5: ...1050 AlarmSaf Product Use When installed in accordance with all standards listed in Section 2 of this document the RMBE battery enclosure provides single or dual battery backup for rack mount applica...

Страница 6: ...V 12V Two separate outputs 24V 24V Two separate outputs 12V and 24V Two separate outputs 12V One single output or 24V One single output VOLTAGE SELECTION BATTERY CONNECT CAUTION ONLY ONE VOLTAGE SELEC...

Страница 7: ...uipment installed The RMBE should be installed near the bottom of the rack to ensure rack stability Install batteries into the RMBE enclosure See Section 4 1 2 Ensure all back panel jumpers are remove...

Страница 8: ...enclosure NOTE When replacing the batteries ALL of the batteries in the enclosure should be replaced at the same time Ensure the new batteries are all of the same voltage and AH capacity Figure 4 1 2...

Страница 9: ...LTAGE SELECTION 4 2 2 Battery Connection Locate the terminal wiring blocks on the back panel of the unit and remove the terminal block from the header there are two locking screws one on either end of...

Страница 10: ...CTION 5 1 1 1 Voltage Selection Jumpers For each battery set only ONE voltage selection jumper must be in place The back panel of the RMBE is labelled for the voltage selection options Each battery se...

Страница 11: ...orrect Verify internal batteries are not damaged and that they are charged replace if necessary Discharged Bad Battery Ensure that all internal wiring of the RMBE is connected properly Internal wiring...

Страница 12: ...ations 6 2 1 Ambient Temperature Range 0 C to 49 C 32 F to 120 F 6 2 2 Ambient Humidity 93 at 32 C 90 F maximum 6 2 3 BTU Output Not Applicable 6 3 Mechanical Specifications 6 3 1 Weight Approx 30 lbs...

Страница 13: ...3 71 0 815 3 250 DETAIL A TYPICAL 4 PLCS DETAIL A 25 1875 1875 0 683 0 75 16 87 Rack Mount Battery Enclosure Installation Instructions 5 27 2009 11 42 41 AM 52 342 Rev A 01 Page 13 of 14 AlarmSaf 65A...

Страница 14: ...erters allow multi voltage system backup with a single battery set DC DC Converter Voltage distribution providing on off control for the outputs Control can be from FAI an access control panel card re...

Отзывы: