25
Screen Display During Normal Operation:
There are two lines on the screen. The
bottom line indicates the position/status
of the device. On the top line, ALARKO
- CARRIER will appear alternately with
4-5 seconds interval, together with the
information on which engines are
running and which ones have stopped.
The automatic operation light and the
running pump light are on.
Fault - Error Messages:
RST Error: This message appears on
the display if the motor remains in two
phases during start-up or operation, or
if the mains connections are incorrect.
Thermal Relay Tripped: This message
appears on the display if the thermal
relay of any of the motors trips. The
number
indicates
which
motor's
thermal relay is tripped. At this time,
the fault light is lit red.
No Water: When the tank is waterless,
the panel cuts power and this warning
appears on the display.
Encrypted Section:
This section is only for use by authorized services. Password can be entered
by typing. Some settings of the water booster are made and historical
information can be learned.
ALDF Water Booster Panel Dimensions
Содержание ALD 400 Series
Страница 1: ...AL D ALDF 400 600 Series WATER BOOSTER Operating Manual...
Страница 2: ...Code No D 3 1 7 Printing Date 301213 Revision No 301213...
Страница 3: ...ALD and ALDF 400 600 Series ALD ALDF 400 600 Series WATER BOOSTER Operating Manual...
Страница 5: ......
Страница 36: ...ELECTRICAL DIAGRAM ALD Series Types 615 10 1 620 8 1 620 9 1 631 6 1 631 7 1 631 8 1 35...