Parameter
Value (unit)
Register address
Access
Data format
DEC
HEX
Time (ms)
—
61563
0xF07B
Read only
UINT 32
New time
Date/Time in
seconds from
January 1, 2000.
61565
0xF07D
Read and write
UINT 32
Write the new
time
0 – do not write;
1 – write
61567
0xF07F
Read and write
UINT 16
Time and date
(UTC)
Date/Time in
seconds from
January 1, 2000.
61568
0xF080
Read only
UINT 32
Time zone
Offset in minutes
from Greenwich
61570
0xF082
Read and write
INT 16
Device status
—
61620
0xF0B4
Read only
UINT 32
MAC-address
—
61696
0xF100
Read only
UINT 48
DNS server 1
—
12
0xС
Read and write
UINT 32
DNS server 2
—
14
0xЕ
Read and write
UINT 32
Assign IP
address
—
20
0x14
Read and write
UINT 32
Enter subnet
mask
—
22
0x16
Read and write
UINT 32
Set the gateway
IP address
—
24
0x18
Read and write
UINT 32
Current IP
address
—
26
0x1A
Read only
UINT 32
Current subnet
mask
—
28
0x1C
Read only
UINT 32
Current gateway
IP address
—
30
0x1E
Read only
UINT 32
DHCP Mode
0 – absolute
prohibition
1 – read only
2 – write only
32
0x20
Read and write
UINT 16
5.5.2 Error codes for Modbus protocol
When working on the Modbus protocol, errors may occur. These errors are described in
. In
case of an error, Module sends a response to the Network Master with an error code.
Table 5.6 List of possible errors
Name
Code
Description
MODBUS_ILLEGAL_
FUNCTION
01 (0x01)
Illegal function code. The error occurs if
Module does not support the Modbus
function specified in the request.
MODBUS_ILLEGAL_DATA_
ADDRESS
02 (0x02)
Illegal register address. The error occurs if
the request contains register addresses
that are not in Module.