– exchange with the Master via the Modbus TCP protocol (port 502) – up to 4 simultaneous
connections with different Network Masters;
– connection and data exchange with a PC using the akYtec Tool Pro.
5.5.1 Modbus TCP communication
Table 5.3 Reading and writing parameters using the Modbus TCP protocol
Operation
Function
Reading
3 (0х03) or 4 (0х04)
Writing
6 (0х06) or 16 (0х10)
The list of Modbus registers is read from the device using the akYtecToolPro program in the “Device
Parameters” tab. This list of Modbus registers is presented in the tables below.
Table 5.4 General Registers for Online Modbus Communication
Name
Register
Size/type/description
Device name (DEV)
0xF000
Character string up to 32
bytes, Win1251 encoding
Firmware version (VER)
0xF010
Character string up to 32
bytes, Win1251 encoding
Platform name
0xF020
Character string up to 32
bytes, Win1251 encoding
Platform version
0xF030
Character string up to 32
bytes, Win1251 encoding
Hardware version
0xF040
Character string up to 16
bytes, Win1251 encoding
Additional character
information
0xF048
Character string up to 16
bytes, Win1251 encoding
Time and date
0xF080
4 bytes, in seconds since 2000
Time zone
0xF082
2 bytes, signed short, offset in
minutes from Greenwich
Serial number
0xF084
Character string 32 bytes,
encoding Win1251, 17
characters are used
Table 5.5 Modbus communication registers
Parameter
Value (unit)
Register address
Access
Data format
DEC
HEX
Mode for output
DO1
0 – switching of a
logic signal;
1 – PWM low
frequency;
2 – PWM high
frequency;
3 – pulse
generator
272
0х110
Read and write
UINT 16
Mode for output
DO2
0 – switching of a
logic signal;
1 – PWM low
frequency;
273
0х111
Read and write
UINT 16