Akse Electrex 96 RS485 Скачать руководство пользователя страница 4

PHASE SEQUENCE

1-2-3

Correct sequence

1-3-2

Incorrect sequence

-----

Indicates that the device is not able to defi ne the sequence

Please consider that:
• 

only the voltage sequence is detected;

• 

the detection considers the hypothesis that the tensions are sinusoidal (or at least 
slightly distorted) and belonging to a symmetrical (or almost) triad;

• 

independently  from  the  insertion  3W/4W,  it  is  considered  exclusively  the  sign  of 
voltage 2 and 3  in the zero-crossing of voltage for phase 1 -  it is not calculated the 
eff ective phase of the voltage fundamentals;

• 

the  phase  sequence  is  indicated  with  the  “L123”,  “L132”,  “L—“  symbols  next  to 
frequency, in the voltages displaying page.

It is assumed:
L1 is the voltage with phase 0°
L2 is the voltage with phase 240° (in delay to L1)
L3 is the voltage with phase 120° (in advance to L1)

S1 S2 S1 S2 S1 S2

I1

I2

I3

L1

L2

L3

P1

P2

S1

S2

S1 S2 S1 S2 S1 S2

I1

I2

I3

L1

L2

L3

P1

P2

S1

S2

P1

P2

S1

S2

S1 S2 S1 S2 S1 S2

I1

I2

I3

L1

L2

L3

P1

P2

S1

S2

P1

P2

S1

S2

P1

P2

S1

S2

3P3W / 3P4W / 3I

3P3W

1P2W / 2P2W

S1 S2 S1 S2 S1 S2

I1

I2

I3

L1

L2

L3

P1

P2

S1

S2

3P3W-B / 3P3W-B-3U

3P4W-B / 3P4W-B-3U

1P2W

2P2W / 3P3W-B

Use cables with max cross-section of 2,5 mm

2

 if stranded, 4 mm

2

 if rigid and connect them 

to the clamps marked VOLTAGE INPUT on the instrument according to the  applicable 
diagrams that follow. 

VOLTAGE CONNECTION

U1 U2 U3

N

VOLTAGE INPUT

L

N

U1 U2 U3

N

VOLTAGE INPUT

L1

L2
L3
N

U1 U2 U3

N

VOLTAGE INPUT

L1

L2
L3

U1 U2 U3

N

VOLTAGE INPUT

L1

L2
L3
N

U1 U2 U3

N

VOLTAGE INPUT

L

N

3P4W / 3P4W-B-3U / 3I

3P3W / 3P3W-B-3U

3I

3P4W-B

U1 U2 U3

N

VOLTAGE INPUT

L1

N

L2
L3

CURRENT CONNECTION

Connect  the  CT  outputs  to  the  terminals  marked  I1,  I2,  I3  (CURRENT  INPUT)  of  the 
instrument according to the applicable diagrams that follow. 

Note:

 Scrupulously respect the matching of phase between the voltage signals and current 

signals. Failure to comply with this correspondence and connection diagrams gives rise to 
measurement errors.

The  instrument  is  equipped  with  a  separate  power  supply.  The  power  supply  terminals 
are numbered (17) and (18).  Use cables with max cross-section of 2,5 mm

2

 if stranded, 

4  mm

2

 if rigid.

POWER SUPPLY

SERIAL LINE CONNECTION

POWER SUPPLY

1

230//- 10% 50/60Hz

2

F: 500 mA T

Max cable length: 1000 meters.

RS485

Address

27

Baud rate

38400

Parity

None

Bit of Stop

2

1

2

VOLTAGE INPUTS

POWER
SUPPLY

RS-485

18

17

V1 V2 V3 N

A B

T

VOLTAGE INPUTS

POWER
SUPPLY

RS-485

18

17

V1 V2 V3 N

A B

T

akse srl

    Via Aldo Moro, 39    42124  Reggio Emilia    Italy

Tel. +39 0522 924 244    Fax +39 0522 924 245    [email protected]    www.akse.it

P.I. 01544980350     R.E.A. 194296      Cap. Soc. Euro 85.800,00 i.v.

Subject to modifi cation without notice. 

Edition 2019 01 28 ENG0260