NOTE n.1

3P4W

3 phases 4 wires

Star

2P2W

2 phases 2 wires

Two-phases

1P2W

1 phases 2 wires

Single phase

3I

3 phases 2 wires

3 Current Inputs  single phase o three phases

3P3W-B-3U

1 phases 3 wires

Balanced triangle 

3P4W-B-3U

1 phases 4 wires

Balanced star

3P3W-B

1 phases 2 wires

Balanced triangle 

3P4W-B

1 phases 2 wires

Balanced star

3P3W

2 phases 3 wires

Triangle

NOTE n.2

POWERS

Integration time of the average value (AVG) and peak value (MD) for 
Power  (from 1 to 60 minutes).

CURRENTS Integration time of the average value (AVG) and peak value (MD) for 

Current  (from 1 to 60 minutes).

NOTE n.3

NORMAL

Classic  Alarm  with  reference  to  a  fi xed  threshold  or  to  maximum  and 
minimum delay and applicable hysteresis. “AVG” parameter is not used. 

UNBAL%

Considers  also  the  2  following  registers  of  the  selected  one  in  “MEAS”.  
“THRE” parameter becomes a % value. Alarm goes on when one of the 
three register is diff erent from the percentage set on “THRE” comply with 
the higher value of the three read register if “MAX” is set on “TYPE”, or 
comply with the lower value of the three register if “MIN” is set on “TYPE” 
With delay and applicable hysteresis.

UNBAL

Considers  also  the  2  following  registers  of  the  selected  one  in  “MEAS”.  
“THRE”  parameter  becomes  a      value. Alarm  goes  on  when  one  of  the 
three register is diff erent from the percentage set on “THRE” comply with 
the higher value of the three read register if “MAX” is set on “TYPE”, or 
comply with the lower value of the three register if “MIN” is set on “TYPE” 
With delay and applicable hysteresis.

3-OF-3

Considers  also  the  2  following  registers  of  the  selected  one  in  “MEAS”. 
It  operates  on  a  fi xed  max  or  min  threshold  with  delay  and  applicable 
hysteresis.  When  all  the  three  registers  exceed  the  threshold  the  alarm 
goes ON. “AVG” parameter is not used.

1-OF-3

Considers  also  the  2  following  registers  of  the  selected  one  in  “MEAS”. 
It  operates  on  a  fi xed  max  or  min  threshold  with  delay  and  applicable 
hysteresis. If one of the three registers exceeds the threshold the alarm 
goes ON. “AVG” parameter is not used.

NOTE n.4

MAX

Alarm setting in excess or in decrease compared with the predefi ned 
conditions.
With the exception of “UNBAL and UNBAL%”.

MIN

NOTE n.5

MEAS

Indicates which register (measure) the alarm is related to.
See table N.1 Input Register.

THRE

Alarm threshold in absolute value, with the exception made for “UNBAL” 
in which the value inserted becomes a percentage.

NOTE n.6

NORMAL

Alarm remains active during the duration of the event. It restores auto-
matically.

HOLD

Alarm remains active until the manual reset via Modbus.

NOTE n.7

ALARM 1

MODBUS alarm (Associated with output 1 if present)

ALARM 2

MODBUS alarm (Associated with output 2 if present)

ALARM 3

MODBUS alarm (Associated with output 3 if present)

ALARM 4

MODBUS alarm (Associated with output 4 if present)

NOTE n.8

LED-1

OFF

The instrument’s LED remains off 

S0-1, 2, 3, 4

The instrument’s LED fl ashes according to the 
selected pulse generator

NOTE n.9

EA

Power (Energy) Active Imported / Exported

ER L

Power (Energy) Reactive Inductive Imported / Exported

ER C

Power (Energy) Reactive Capacitive Imported / Exported

ES

Power (Energy) Apparent Imported / Exported

EA+

Power (Energy) Active Imported

ER L+

Power (Energy) Imported Inductive Reactive

ER C+

Power (Energy) Imported Reactive Capacitive

ES+

Power (Energy) Apparent Imported

EA-

Power (Energy) Active Exported

ER L-

Power (Energy) Exported Inductive Reactive

ER C-

Power (Energy) Capacitive Reactive

ES-

Power (Energy) Apparent Exported

NOTE n.10

YES

Referred to the primary of the current transformer (CT)

NO

Referred to the secondary of the current transformer (CT)

ALARM SETUP EXAMPLE

Alarm (latching) when the average active power (MEAS 344) exceeds the value of 100 
kW, hysteresis of 5% and delay of 5 seconds; set the parameters as in the table:

ALARM 1

 (

note n.7)

MODE (

note n.3)

NORMAL, UNBAL%, UNBAL,
3-OF-3, 1-OF-3

NORMAL

DIRECTION (

note 

n.4)

MAX, MIN

MAX

DATA ADDRESS 
(

note n.5)

Controlled measure. See table n.1 for register 
selection

344

THRESHOLD (

note 

n.5)

Threshold value

+100.0 K

HYSTERESIS

1...99 (%)

05

ON DELAY

1 sec ...99 minutes

05 SEC

OFF DELAY

1 sec ...99 minutes

01 SEC

OUT MODE (

note 

n.6)

NORMAL, HOLD

NORMAL

INPUTS - OUTPUTS 

INPUTS

OUTPUTS

10

C2 Common2 (negative)

19

C1 Common1 (negative)

11

I2 Input 2 (positive)

20

O1 Output 1 (positive)

12

C1 Common1 (negative)

21

C2 Common2 (negative)

13

I1 Input 1 (positive)

22

O2 Output 2 (positive)

INPUTS

OUTPUTS

Supply voltage (external):

from 10 to 30 
Vdc

Maximum applicable voltage:

27 Vdc

Current consumption:

from 2 to 10mA Maximum switchable current:

27mA

Max. count frequency

10 or 100Hz

N.B. For gas meters a galvanic separation is 
needed per ATEX standards

N.B. Transistor optocoupler digital outputs (NPN) 
according to DIN 43864.

Common

230 V~

24V =

N L

- +

12

20

19

10 11

AUX IN/OUT

21

13

22

Reactive energy

Active energy

C1

C2

NO

C

NC

R

e

l

a

y

NO

C

NC

R

e

l

a

y

230 V~

24V =

N L

- +

12

20

19

10 11

AUX IN/OUT

21

O2

O1

13

22