Aksa AGM 100 Скачать руководство пользователя страница 48

13

8.3  LOADING

When planning the electrical distribution system, it is important to
ensure that a balanced load is presented to the generating set. If
loading on one phase is substantially higher than the other phases
it will cause overheating in the alternator windings, imbalance in
the phase to phase output voltage and possible damage to sensitive
3 phase equipment connected to the system. Ensure that no
individual phase current exceeds the current rating of the generating
set. For connection to an existing distribution system, it may be
necessary to reorganize the distribution system to ensure these
loading factors are met..

8.4  POWER FACTOR

The power factor (cos

j

) of the connected load should be determined.

Power factors below 0.8 lagging (inductive) can overload the
generator. The set will provide its kilowatt rating and operate
satisfactorily from 0.8 lagging to unity power factor (1.0). Particular
attention must be given to installations with power factor correction
equipment such as capacitors to ensure that a leading power factor
is never present. This will lead to voltage instability and may result
in damaging overvoltages. Generally  whenever the generating set
is supplying the load any power factor correction equipment should
be switched off.

8.5 GROUNDING/EARTHING REQUIREMENTS

The frame of the generating set must be connected to an earth
ground. Since the set is mounted on vibration isolators, the ground
connection must be flexible to avoid possible breakage due to
vibration.
Ground connection cables or straps should have at least full load
current carrying capacity and meet applicable regulations.

8.6 ALTERNATOR RECONNECTION

Most alternators can be reconnected to suit different output
voltages. Ensure that all other components such as circuit breakers,
current transformers, cables and ammeters are suitable before
operating at a different voltage.

8.7 PARALLEL RUNNING

Extra equipment must be fitted for the standard generating sets
to be operated in parallel with other generating sets or with mains
power.

8.8 INSULATION TEST

Before starting the generating set after installation, test the insulation
resistance of the windings. The Automatic Voltage Regulator (AVR)
should be disconnected and the rotating diodes either shorted out
with temporary links or disconnected. Any control wiring must also
be disconnected.
A 500V Megger or similar instrument should be used. Disconnect
any earthing conductor connected between neutral and earth and
megger an output terminal to earth. The insulation resistance should
be in excess of 1M   to earth. Should the insulation resistance be
less than 1M   the winding must be dried out.

Table 8.1 

Current carrying capacity of power cables 

(PVC - ISOLATED CABLES YVV

(NYY) SUTABLE TO 0.6/1 KV VDE NORMS AND TS)

CABLE

SECTION

(mm

2

)

0,6/1 KV, NYY TYPE CABLE CURRENT CAPACITY

2.5

4
6

10
16
25
35
50
70
95

120
150
185
240

Soil

25°C

 

at air

36
46
58
77

100
130
155
185
230
275
315
355
400
465

25
34
44
60
80

105
130
160
200
245
285
325
370
435

Multiple

Core

Multiple

Core

Multiple

Core

Single

Core

40°C

 

at air

22
30
38
53
71
94

114
138
176
212
248
238
322
380

25
33
42
57
76

101
123
155
191
228
267
305
347

-

21
28
36
50
67
88

110
138
170
205
245
271
310

-

HO7RN-F

Table 8.2 

Recommended cable cross section.

STAND-BY POWER

FULL LOAD CURRENT

CABLE CURRENT CAPACITY

RECOMMENDED

(kVA)

(Ampere)

(Ampere)

CABLE SECTION

U=400 Vac COS     = 0,8

(mm

2

)

GENERATING SETS

24 - 30

38

71

4 x 16

35 - 40

61

71

4 x 16

60 - 65

103

114

3 X ( 35 / 16 )

80 - 85

122

138

3 X ( 50 / 25 )

95 - 105

150

176

3 X ( 70 / 35 )

120 - 130

180

212

3 X ( 95 / 50 )

j

13

8.3  LOADING

When planning the electrical distribution system, it is important to
ensure that a balanced load is presented to the generating set. If
loading on one phase is substantially higher than the other phases
it will cause overheating in the alternator windings, imbalance in
the phase to phase output voltage and possible damage to sensitive
3 phase equipment connected to the system. Ensure that no
individual phase current exceeds the current rating of the generating
set. For connection to an existing distribution system, it may be
necessary to reorganize the distribution system to ensure these
loading factors are met..

8.4  POWER FACTOR

The power factor (cos

j

) of the connected load should be determined.

Power factors below 0.8 lagging (inductive) can overload the
generator. The set will provide its kilowatt rating and operate
satisfactorily from 0.8 lagging to unity power factor (1.0). Particular
attention must be given to installations with power factor correction
equipment such as capacitors to ensure that a leading power factor
is never present. This will lead to voltage instability and may result
in damaging overvoltages. Generally  whenever the generating set
is supplying the load any power factor correction equipment should
be switched off.

8.5 GROUNDING/EARTHING REQUIREMENTS

The frame of the generating set must be connected to an earth
ground. Since the set is mounted on vibration isolators, the ground
connection must be flexible to avoid possible breakage due to
vibration.
Ground connection cables or straps should have at least full load
current carrying capacity and meet applicable regulations.

8.6 ALTERNATOR RECONNECTION

Most alternators can be reconnected to suit different output
voltages. Ensure that all other components such as circuit breakers,
current transformers, cables and ammeters are suitable before
operating at a different voltage.

8.7 PARALLEL RUNNING

Extra equipment must be fitted for the standard generating sets
to be operated in parallel with other generating sets or with mains
power.

8.8 INSULATION TEST

Before starting the generating set after installation, test the insulation
resistance of the windings. The Automatic Voltage Regulator (AVR)
should be disconnected and the rotating diodes either shorted out
with temporary links or disconnected. Any control wiring must also
be disconnected.
A 500V Megger or similar instrument should be used. Disconnect
any earthing conductor connected between neutral and earth and
megger an output terminal to earth. The insulation resistance should
be in excess of 1M   to earth. Should the insulation resistance be
less than 1M   the winding must be dried out.

Table 8.1 

Current carrying capacity of power cables 

(PVC - ISOLATED CABLES YVV

(NYY) SUTABLE TO 0.6/1 KV VDE NORMS AND TS)

CABLE

SECTION

(mm

2

)

0,6/1 KV, NYY TYPE CABLE CURRENT CAPACITY

2.5

4
6

10
16
25
35
50
70
95

120
150
185
240

Soil

25°C

 

at air

36
46
58
77

100
130
155
185
230
275
315
355
400
465

25
34
44
60
80

105
130
160
200
245
285
325
370
435

Multiple

Core

Multiple

Core

Multiple

Core

Single

Core

40°C

 

at air

22
30
38
53
71
94

114
138
176
212
248
238
322
380

25
33
42
57
76

101
123
155
191
228
267
305
347

-

21
28
36
50
67
88

110
138
170
205
245
271
310

-

HO7RN-F

Table 8.2 

Recommended cable cross section.

STAND-BY POWER

FULL LOAD CURRENT

CABLE CURRENT CAPACITY

RECOMMENDED

(kVA)

(Ampere)

(Ampere)

CABLE SECTION

U=400 Vac COS     = 0,8

(mm

2

)

GENERATING SETS

24 - 30

38

71

4 x 16

35 - 40

61

71

4 x 16

60 - 65

103

114

3 X ( 35 / 16 )

80 - 85

122

138

3 X ( 50 / 25 )

95 - 105

150

176

3 X ( 70 / 35 )

120 - 130

180

212

3 X ( 95 / 50 )

j

Содержание AGM 100

Страница 1: ......

Страница 2: ......

Страница 3: ......

Страница 4: ...r 5 4 7 ase 5 4 8 Titre im zolat rleri 5 4 9 Susturucu ve Egzoz Sistemi 5 4 10 Kontrol Sistemi 5 5 YERLE T RME KALDIRMA VE DEPOLAMA 6 5 1 Genel 6 5 2 Kabin 6 5 3 Jenerat r n Ta nmas 6 5 4 Jenerat r Ye...

Страница 5: ...k Eleman 14 12 12 So utma Sistemi So utma Suyu Seviyesi 14 13 UYARILAR 16 13 1 Radyat r 16 13 2 Fan Kay lar 16 13 3 Serpatin Kay 16 13 4 V Tipi Kay 16 13 5 Ate leme Sistemleri Ate leme Sistem Tipleri...

Страница 6: ...g venlik sorumlulu u jenerat r kuran i leten ve bak m n yapan ki ilere aittir E er belirtilen g venlik nlemleri uygulanm ise kaza ihtimali ok azd r Herhangi bir teknik operasyon veya i lem yapmadan n...

Страница 7: ...2 UYARILAR Jenerat r odas n uygun ekilde havaland r n z Jenerat r mahalinde mutlaka gaz ka ak alarm cihaz tak lmal ve jenerat r panosuna ba lanmal d r Jenerat r jenerat r odas ve zeminini temiz tutunu...

Страница 8: ...kalifiye olan yetkili bir elektrik i taraf ndan ilgili elektrik kodlar na ve standartlar na uygun bir ekilde yap lmal d r Jenerat r al t rmadan nce jenerat r n topraklanmas n n yap ld ndan emin olunu...

Страница 9: ...Kazezadeye dakikada ortalama 10 defa nefes veriniz E er yard m a rmak i in kazazede yaln z b rak lacaksa 10 defa nefes vererek k sa zamanda geri d n n z ve nefes verme i lemine devam ediniz Her 10 ne...

Страница 10: ...sarg lar n so utmak i in dahili bir fan mevcuttur 5 4 6 Alternat r Jenerat r n k gerilimi ve g c IP 21 koruma standard nda tanecik ve damlama suya kar korumal kafes korumal kendinden ikazl kendinden...

Страница 11: ...il 5 1 Jenerat r n vin ile kald r lmas Ya mur kar sulusepken sel suyu direk g n dondurucu so uk ve a r s cakl k gibi unsurlara kar korumal olmal d r A nd ran veya iletkenlik sa layan toz iplik duman y...

Страница 12: ...vermemesi i in odan n d na sevk etmek ve g r lt y azaltmakt r Motorun g r lt seviyesini azaltmak i in uygun bir egzoz susturucusu egzoz borusuna tak lmal d r UYARILAR Motor egzoz gaz n n solunmas tehl...

Страница 13: ...at r zerinde bulunan gaz hatt ile ana gaz hatt aras gaz flexi ile ba lanmal d r UYARILAR Jenerat rlerin gaz hatlar standartlara uygun olmal ve ka ak kontrol nden ge irilmi olmal d r Gaz hatt n n ve je...

Страница 14: ...iri ve k pencerelerinin boyutlar MODEL Stand By G c kVA ODA BOYUTU mm HAVA G R PENCERES TOPLAM ALANI m2 AGM 25 AGM 35 AGM 60 AGK 80 AGM 100 25 37 62 82 100 4500 4500 5000 5000 5000 0 50 0 50 0 50 0 70...

Страница 15: ...ce negatif terminal ak den s k lmelidir Ak ler jenerat re m mk n oldu unca yak n konulmal d r E er ak ler jenerat rden uzak noktalara konulursa istenmeyen voltaj d meleri meydana gelir ve buna ak leri...

Страница 16: ...d r Titre imden dolay meydana gelebilecek kopmalar nlemek i in toprak ba lant s esnek olmal d r Topraklama kablolar standartlar kar lamal ve en az ndan tam y k ak m n ta yabilecek kapasitede olmal d r...

Страница 17: ...SUYU ISITICISI 12 JENERAT R BAKIMI 12 1 Ba lang al t rma Bak m Ba lang al t rma kontrol i lemleri motoru hizmete almadan nce yap lmal d rlar L tfen tabloda verilen Bak m Program na bak n z ve 1 kolon...

Страница 18: ...n Temizleyin Kay lar ve Kay Gerginliklerini Kontrol Edin Gaz Govern r ve Jikle Hatlar n Ya lay n Sadece Karb rat rl Motorlar R lanti Devrini Kontrol Edin ve Ayarlay n Sadece Karb rat rl Motorlar Hava...

Страница 19: ...unuz motoru al t r n z ve ya tahliye tapas nda yada ya filtre contas nda ya ka a olup olmad n kontrol ediniz Herhangi bir ya ka a varsa durdurmak i in gereken ekilde s k n z 12 10 Motor Hava Filtresi...

Страница 20: ...3 32500292 32500292 32500058 32500058 32500111 32500111 101021 101021 32500020 32500020 P 25 veya E de er PF 47 PF 52 veya E de er PF 1218 veya E de er PF 1218 veya E de er PF 454 veya E de er Motor 1...

Страница 21: ...ilde al mas n nleyerek a r s nmaya neden olur 13 3 Serpantin Kay Bu kay ta atlak veya kanall taraf nda t rt llanma olup olmad d zenli olarak kontrol edilmelidir atlak veya t rt llanma var ise kay de i...

Страница 22: ...8 1 L Zenith Do al Gaz Mikseri Zenith Karb rat rl 015052 w ift Yak t Sistemi Holley Karb rat r 0 7448 Elektrikli Jikle Holley Karb rat r 0 82010 Elektrikli Jikle Impco LPG Yak t Sistemi Nolff LPG Yak...

Страница 23: ...temiz tutunuz Radyat r hava k davlumbaz n kontrol ediniz t kan k ise a n z ve n nde hava k na mani olan ne varsa uzakla t r n z 14 JENERAT R ALI TIRMADAN NCE YAPILMASI GEREKEN KONTROL VE LEMLER Jenera...

Страница 24: ...taj normal limitlerin d na kt nda start gecikmesi s resinin sonunda mod l n paneli zerindeki LED g stergesi s necektir ebeke ar zas nda veya uzaktan start sinyalinin gelmesi durumunda a a daki i lem s...

Страница 25: ...R ALI TIKTAN SONRA YAPILACAK LEMLER Jenerat rde ola an d bir ses veya titre im olup olmad n kontrol ediniz Gaz hatt nda ka ak olup olmad n kontrol ediniz Motor s cakl ve ya bas n durumlar n pano zeri...

Страница 26: ...H z D k H z Yard mc Alarm Elektrik A ma A r Ak m kaz Y ksek Voltaj AC D k Voltaj AC Y ksek Frekans D k Frekans IKONLAR VE LCD TANIMLARI BASMALI BUTONLAR DURUM G STERGE SEMBOLLER ALARM G STERGELER v v...

Страница 27: ...minal ak m de erini kesinlikle a mamal d r Transfer Sivi Pano Yerle tirilmesi Jenerat r i in kullan lacak kuvvet kablolar n n ak m ta ma kapasiteleri verilmi tir Transfer sivi panosu jenerat rden ayr...

Страница 28: ...et Y kte iken alternat r voltaj d k Voltaj ayar potansiyometresi ayars z Regulat r korumas devrede Reg lat r ar zal D ner diodlar ar zal Voltaj potansiyometreden ayarla A r ak m g fakt r 0 8 den k k m...

Страница 29: ...e NG motorlar i in Valfler s k m Valfler yanm Valf yay k r lm MOTOR ARIZALARI VE G DER LMES Motor al yor ve Duruyor Ate leme svici kontaklar ar zal Gaz sistemi k smen t kal Hava s z nt s var Motor k G...

Страница 30: ...erine yapt r lmal d r Jenerat re ait bak m izelgesi ve bak m kitap klar makine ile birlikte m teriye teslim edilmi tir S z konusu bak m kitap ve izelgesinin kaybolmas durumunda m teri bu kitap klar te...

Страница 31: ...klenmemesi durumunda olu an ar zalardan m teri sorumludur 16 Sat n al nan jenerat rlere garanti s resi i erisinde orijinal ekipmanlar ve projesi haricinde ilave ekipman ve proje yap lamaz Yap lmas pla...

Страница 32: ...27...

Страница 33: ...NOTLAR...

Страница 34: ......

Страница 35: ......

Страница 36: ...5 Grounding Earthing Requirements 13 8 6 Alternator Reconnection 13 8 7 Parallel Running 13 8 8 Insulation Test 13 9 ACOUSTIC SILENCING 14 9 1 Exhausts Silencers 14 9 2 Canopies 14 9 3 Other Sound Att...

Страница 37: ...parts 2 SAFETY 2 1 General The generating set is designed to be safe when used in the correct manner However responsibility for safety rests with the personnel who install use and maintain the set If...

Страница 38: ...LING This manuel covers procedures for installation and handling of generating sets That chapter should be read before installing moving and lifting the generating set The following safety precautions...

Страница 39: ...ems that are compatible with its electrical characteristics and that are within its rated capacity Keep all electrical equipment clean and dry Replace any wiring where the insulation is cracked cut ab...

Страница 40: ...pull the plug or the cable away from the viation If this is not possible stand on dry insulating material and pull the victim clear of the conductor preferably using insulated material such as dry woo...

Страница 41: ...isolators are fitted between the engine alternator feet and the baseframe 4 9 SILENCER AND EXHAUST SYSTEM An exhaust silencer is provided loose for installation with the generating set The silencer a...

Страница 42: ...ostatic polyester powder paint Exhaust silencer is protected against envirenmental influences and an emergency stop push button is installed on canopy Canopy enables easy lifting maintenance and opera...

Страница 43: ...e pad provides a rigid support to prevent deflection and vibration Typically the foundation should be 150 mm 6 inches deep and at least as wide and long as the generating set The ground or floor below...

Страница 44: ...afety requirements Ensure that fumes from the exhaust outlet will not be a hazard In designing an exhaust system the primary consideration is to not exceed the allowable back pressure permitted by the...

Страница 45: ...odel AGM 25 AGM 35 AGM 60 AGK 80 AGM 100 Stand By Power kVA Room Dimensions mm Air Inlet Openings Total Area m2 25 37 62 82 100 4500 4500 5000 5000 5000 0 5 0 5 0 5 0 8 0 8 With Length Height 4000 400...

Страница 46: ...rformance and duability it is important that you use only engine lubricating oils of the correct quality in your engine Proper quality oils also provide maximum efficiency for crankcase ventilation sy...

Страница 47: ...ith vaseline 2 Check if any untightened connections exist 8 ELECTRICAL CONNECTION Only fully qualified and experienced electrical technicians should carry out electrical installation service and repai...

Страница 48: ...0 65 103 114 3 X 35 16 80 85 122 138 3 X 50 25 95 105 150 176 3 X 70 35 120 130 180 212 3 X 95 50 j 13 8 3 LOADING When planning the electrical distribution system it is important to ensure that a bal...

Страница 49: ...ST SILENCERS As discussed in Section 5 8 the exhaust silencer will decrease sound levels from the engine 9 2 CANOPIES Section 5 2 discusses sound attenuating canopies that lower the noise level of the...

Страница 50: ...il film to accumulate on any internal or external surfaces Wipe down surfaces using an aqueous industrial cleaner 13 GENERAL PRECAUTIONS AND CONTROLS WHICH MUST BE DONE BEFORE STARTING UP THE GENERATI...

Страница 51: ...iated After the Fuel Solenoid is energized then1 2 second later the starter motor is engaged The engine is cranked for 10 second If the engine fails to fire during this cranking attempt than the start...

Страница 52: ...the engine stalling or alternator winding insulation of formation or burning can occur o Set the alternator outlet circuit breaker on the circuit to OFF position before stop the generating set o Cont...

Страница 53: ...speed Auxiliary Alarm Warning or Shutdown Electrical Trip High Current Warning Over Voltage AC v v A Hz Hz v v Over Frequency Under Frequency Under Voltage AC Phase Phase Neutral Phase Phase Pressure...

Страница 54: ...Current from one phase should not exceed the nominal current Current from one phase should not exceed the nominal current Two different power cables which will be used between the generating set and...

Страница 55: ...engine speed Check wingings High voltage at no load Voltage potentiometer out of setting Failed regulator Reset voltage Substitude regulator Failed regulator Rotating bridge failure Substitude regula...

Страница 56: ...ction system Fault in cold start system Restriction in exhaust pipe Engine temperature is too low Incorrect valva tip clearances Engine over load Blue or white exhaust smoke Wrong grade of lubrication...

Страница 57: ...Belts and Belt Tension Lubricate Throttle Governor Choke Linkage Carbureted Engines Only Check Adjust Idle Speed Carbureted Engine Only Inspeck Clean Air Cleaner Element Replace Primary Air Cleaner E...

Страница 58: ...t An equivalent oil filte must be used when servicing the engine see Engine Specifications for the recommended oil filter for your engine The filter protects your engine from harmful abrasive or sludg...

Страница 59: ...amage to the system Radiator Inspect the exterior of the radiator for obstructions Remove all bugs dirt or foreign material with a soft brush or cloth Use care to avoid damaging the core fins If avail...

Страница 60: ...in and valve stem seals cut nicked or worn out If the engine is running rich the exhaust smoke will be a sooty black color and it will smell like gasoline on gasoline engines ENGINE STORAGE 1 One to...

Страница 61: ...ectric Choke Impco LPG Fuel System Nolff LPG Fuel System PSI Fuel Injection Gasoline PSI Fuel Injection LPG Mixer Dual Filter Impco Natural Gas Mixer Zenith Z E E M S Fuel Injection 1 6 L 3 0 L 4 3 L...

Страница 62: ...or voltage Regulation GENERATING SETS 231 400 V 50 Hz GROUP NATURALGAS LPG ENGINE Litre mbar AGM 25 AGM 40 AGM 60 AGM 80 AGM 100 Power Air Intake Flow Engine Oil Capacity Naturalgas Pressure min Stand...

Страница 63: ...FILL OR HARDENING BY LEAVING UNCHARGED ON MANUAL GENERATING SETS NEVER START OR STOP THE DIESEL ENGINE WHEN THE GENERATING SET IS UNDER LOAD ENGINE SHOULD BE STARTED AND STOPPED AFTER LOAD IS DISCONN...

Страница 64: ...29...

Страница 65: ......

Страница 66: ......

Страница 67: ......

Страница 68: ......

Страница 69: ......

Страница 70: ......

Страница 71: ......

Страница 72: ......

Страница 73: ......

Страница 74: ......

Отзывы: