Description
Units
Min
Def
Max.
Set Point
(ºC/ºF)
–40
0.0
320
Sensor 1 differential
(ºC/ºF)
0.1
1.0
20.0
Calibration of probe 1
(ºC/ºF)
–20.0
0.0
20.0
Set point upper limit (it cannot be set above this value)
(ºC/ºF)
B.I.
99.9
320
Set point lower limit (it cannot be set below this value)
(ºC/ºF)
–40.0 –40.0
B.S.
Compressor protection
OFF/ON
(From the last disconnection)
ON
(to the connection)
OFF/ON
Protection delay time
(min.)
0
0
255
Compressor ON fault s1
(If it is 0, it will always be stopped)
(min.)
0
10
255
Compressor OFF fault s1
(If it is 0, it will always be running)
(min.)
0
5
255
Stop when opening door?
(It requires a digital input configured as door contact)
No
Description
Units
Min
Def
Max.
Defrost type:
Electrical heater
Reverse cycle
Res
Defrost count:
Frequency
Compressor sum
Real time clock
Fre.
Defrost frequency (Time between two starts)
(h.)
0
6
120
Defrost duration
(min.)
0
30
255
Defrost message:
Current temperature
Defrost Start temperat
DEFROST message
DEF
Message duration (Time added at the end of the defrost)
(min.)
0
5
255
Defrost final temperature
(ºC/ºF)
–40.0
8.0
99.9
Defrost at Start-up
No
Defrost delay at Start-up
(min.)
0
0
255
Signals end defrost time
No
Drip time
(min.)
0
1
255
REFRIGERATION control (Compressor)
DEFROST control
Parameters
SET
........5 seg.
SET
SET