Programming menu
The programming menu allows adjusting the unit's parameters to the installation's needs.
Press the
SET
key for 5 seconds to access the programming menu. If the access code is activated, a 2 digit code is
requested, if the code entered is not correct the unit will not enter programming.
The parameters are grouped by functions in 12 separate menus, to access a given menu, select it using the browser and
press
SET
(For more details, consult page 22).
Function of the keys in programming
Basic initial configuration
G
Set point (SP)
It defines the temperature that should be inside the cold storage room:
Ÿ
Minimum: –40.0 *
Ÿ
Maximum: 320 *
*(Depends on the bottom/top locking of the set point).
Calibration of Probe 1
It allows correcting the temperature detected by probe 1, this is particularly useful when the probe cannot be
located in the ideal place.
v
Pressure controller config.
It chooses the correct option depending on the type of pressure switch and their connection (See page 19):
Ÿ
Combined HP-LP: A HP-LP pressure switch is used.
Ÿ
LP indep. AC input: The low pressure switch is separate and is connected to the AC input (Terminal 22).
Ÿ
LP indep digital input: The low pressure switch is separate and is connected to the digital input 2.
q
Connected sensors
Choose the correct option according to the no. of probes connected:
Ÿ
Sensor 1: If it has just one control probe. Defrost will end by time.
Ÿ
Sensor 1 and 2: If it has two probes, a control probe and another one for defrost (evaporator).
Ÿ
Sensor 1 and 3: If it has two probes, one for control and another for data logging or product temperature
(according to
Probe setting
), defrost will finish by time.
Ÿ
Sensor 1, 2 and 3: If it has three probes, one for control, and another for defrost and another for data
logging or product temperature (according to
Probe setting
).
Moves the selection down or decreases the value of
the parameter.
Moves the selection to the right.
Displays the help for the selected parameter or
function.
Moves the selection up, or increases the value of the
parameter.
Moves the selection to the left.
Accepts the value or accesses the selected menu.
Allows exiting a parameter without saving the
changes, returning to the previous menu or exiting
programming.
SET
SET
SET
SET
SET
ESC
¿
20