Level 1

Menus and Description

rE

Level 2

Control 

Level 3

Description

Values Min. Def. Max.

SP

Set Point temperature

(ºC/ºF) -58.0 0.0

211

C0

Sensor 1 calibration (Offset)

(ºC/ºF) -20.0 0.0

20.0

C1

Sensor 1 differential (Hysteresis)

(ºC/ºF)

0.1

2.0

20.0

C2

Set Point upper limit

(ºC/ºF)

C3

99.9 211

(It cannot be set above this value)

C3

Set Point lower limit

(ºC/ºF) -58.0 -50.0 C2

(It cannot be set below this value)

C4

Relay protection delay type:

0

0

1

0=OFF/ON (From the last switch-off)    1=ON (At switch-on)

C5

Protection delay time

(min.)

0

0

255

(Value for the option selected in parameter C4)

C7

Relay time in ON in case of faulty sensor

(min.)

0

10

255

(If C7=0 and C8=/0, the relay will always be OFF disconnected)

C8

Relay time in OFF in case of faulty sensor

(min.)

0

5

255

(If C8=0 and C7=/0, the relay will always be ON connected)

C9

Continuous cycle duration

(h.)

1

1

24

C10

Compressor stops when opening door?    (0 = No)    (1 = Yes)

0

0

1

dEF Level 2

DEFROST control 

Level 3

Description

Values Min. Def. Max.

d0

Defrost frequency (Elapsed time between 2 starts)

(h.)

0

6

120

d1

Defrost maximum duration

(min.)

0

30

255

Type of message during defrost:

d2

(0=Current temperature display)

0

2

2

(1=Defrost start temperature display)

(2=Display dEF message)

d3

Message maximum duration 

(min.)

0

5

255

(Time added at the end of defrost)

d4

Defrost final temperature by sensor 2 

(ºC/ºF) -58.0 8.0

211

Defrost start-up on equipment switch-on:

d5

(0 = No, first defrost according to d0)

0

0

1

(1 = Yes, first defrost according to d6)

d6

Defrost start-up delay on equipment switch-on

(min.)

0

0

255

d7

Defrost type:

0

0

1

(0=Electrical heater)      (1=Hot gas by-pass)

Time calculation between defrost periods:

d8

(0 = Total real time)

0

0

1

(1 = Compressor operation sum)

d9

Drip time, compressor stops and FAN 

(min.)

0

1

255

relay off when defrost ends

FAn Level 2

FANS control (Evaporator)

Level 3

Description

Values Min. Def. Max.

F0

Fans stop temperature by sensor 2

(ºC/ºF) -58.0 4.0

211

If sensor 2 is programmed in P4

F1

Sensor 2 differential 

(ºC/ºF)

0.1

1.0

20.0

F2

Stop fans, when compressor stops?    (0=No)    (1=Yes)

0

0

1

F3

Fans status during defrost  

0

0

1

(0 = Off)  (1 = On)

F4

Start-up delay after defrost

(min.)

0

3

255

Operates if it is higher than d9

F5

Stop fans if the door opens?    (0 = No)    (1 = Yes)

0

0

1

AL

Level 2

ALARM control (Visual)

Level 3

Description

Values Min. Def. Max.

Configuration of temperature alarms

A0

(0=Relative to SP)  (1=Absolute)

0

0

1

(If A0=0, A1 and A2 range from 0 to 50 ºC/ºF)

A1

Maximum alarm in sensor 1

(ºC/ºF)

A2

0.0

211

Level 2

Parameters

- In the desired menu of LEVEL 1 MENUS,

press

key. LEVEL 2 PARAMETERS

programming is accessed. The first para-

meter of the selected menu is displayed

on the screen.

- Press

key to access the next parame-

ter and

key to return to the previous

one.

- Pressing

key, the controller returns to

the LEVEL 1 MENUS

Level 3

Values

- To DISPLAY the CURRENT VALUE of any

parameter, select the required one and

press

key. Once it is displayed, you

can CHANGE VALUE, pressing

or

key.

- Press

key to ACCEPT THE NEW. The

programming returns to LEVEL 2 PARA-

METERS.

- Pressing

key, the controller returns to

the LEVEL 2 PARAMETERS

Nos reservamos el derecho de suministrar materiales que pudieran diferir levemente de los
descritos en nuestras Hojas Técnicas. Información actualizada en nuestra web:

www.ako.com

.

Av. Roquetes, 30-38  |  08812 Sant Pere de Ribes  |  Barcelona  |  España
Tel. (34) 938 142 700  |  Fax (34) 938 934 054  |  e-mail: [email protected]  |  

www.ako.com

Apartado (P.O. Box), 5  |  08800 Vilanova i la Geltrú  |  Barcelona  |  España

AKO ELECTROMECÀNICA, S.A.L.

351463202  REV

.02    2007

D.L.: B-9221-07

7- Parameters transfer

Portable server
AKO-14918

portable server, with no power

supply, in which parameters programmed in a

powered controller can be copied by transfer.

Parameters can be transferred again from the

server to other identical powered controllers.

Storage dump or fast copy of the para-

meters entered in the portable server

to the controller:

Press the key

while the controller is being connected to the power supply until the dis-

play shows 

CPY

, indicating that the transfer was made correctly. Disconnect the controller

and reconnect it to the power supply.
Storage dump can also be done from parameter L6=2.

8- Maintenance

Clean the controller surface with a soft cloth, soap and water. Do not use abrasive deter-

gents, petrol, alcohol or solvents.

9- Warnings

The use of the unit without observing the manufacturer's instructions may alter its safety

qualification.
To ensure correct operation of the apparatus, only NTC type probes supplied by AKO should

be used.
Between -40 ºC and +20 ºC, when the NTC probe is extended up to 1.000 m with minimum

0,5 mm

2

cable, deviation will be less than 0.25 ºC (Probe extension cable ref.

AKO-15586

)

REMARK:

When time parameters are modified, the new values are applied when the current

cycle is completed. In order for it to have an immediate effect, switch the controller off and

then on again.

A2

Minimum alarm in sensor 1

(ºC/ºF) -58.0 0.0

A1

A3

Temperature alarm delay in the start-up

(min.)

0

0

255

(If programmed in A1, A2)

A4

Temperature alarm delay from 

(min.)

0

0

255

the end of a defrost

A5

Temperature alarm delay from the

(min.)

0

30

255

moment at which they should operate due to temperature

A6

Temperature alarm delay from digital input disabling

(min.)

0

0

255

If programmed as “Door contact”

A7

Temperature alarm delay from digital input enabling

(min.)

0

0

255

If programmed as “Door contact”

A8

Signals if defrost ends due to maximum time     (0=No)    (1=Yes)

0

0

1

A10

Differential Alarms Temperature A1 and A2

0.1

1.0

20.0

InP

Level 2

DIGITAL INPUTS

Level 3

Description

Values Min. Def. Max.

Digital Input Nº1 configuration 

(0=Disabled) (1=Door Contact)

i1C

(2=External alarm) (3=Severe external alarm)

0

0

5

(4=Remote defrost)  

(5=Change of set point iS1 + it1)

i1d

Alarm delay of digital Input Nº 1

(min.)

0

0

255

Polarity of digital input Nº1  

i1P

(0=Activated on closing contact)     

0

0

(1=Activated on opening contact)

iS1

Value of auxiliary set point 1 of “COOL” Relay (Compressor) 

(ºC/ºF) -58.0 0.0

211

it1

Duration of auxiliary set point 1

(min.)

0

0

255

CnF Level 2

GENERAL STATUS 

Level 3

Description

Values Min. Def. Max.

P1

Delay of all functions on power supply 

(min.)

0

0

255

switch on

P2

Allocation of password to Set Point:

0

0

1

(0=Without allocation)    (1=With allocation of L5 password)

P3

Initial parameters:

0

0

1

(1=YES, configure to “Def” and exit programming)

P4

Connected sensors

1

2

2

(1 = Sensor 1)  (2 = Sensor 1 + Sensor 2)

P5

Address for units with communication 

0

0

255

Temperature display mode:

P7

(0=Integers in ºC)   (1=One decimal in ºC)

0

1

3

(2=Integers in ºF)   (3=One decimal in ºF)

P8

Sensor to be displayed    (1=Sensor 1)     (2=Sensor 2)

1

1

2

tid

Level 2

ACCESS AND INFORMATION control

Level 3

Description

Values Min. Def. Max.

L5

Access password to parameters and information

0

0

255

L6

Parameters transfer:

(0=Disabled)        (1=Send)     (2=Receive)

0

0

2

PU

Program version (Information)

6- Description of parameters and messages

Values in the 

Def.

column are factory-set.

CHANGE NUMBER

DISPLA

Y

VALUE

PASSWORD

REQUEST

ENTER

PASSWORD

DISPLAY

PASSWORD

CURRENT

VALUE

NEW

VALUE

IF 

L5=0

A

CCEPT

DE NEW

CURRENT

TEMPERATURE

LEVEL 2

PARAMETERS

LEVEL 3

VALUES

EXIT TO

LEVEL 1

A

CCEPT

PASSWORD

PASSWORD

IF PROGRAMMED

CHANGE V

ALUE

LEVEL 1

MENUS

10 Sec.

EXIT

PROGRAMMING

A

CCEPT

A

CCEPT

SIMULTEANOUSLY

EXIT TO

LEVEL 2

REMARK:

If no key is pressed for 25 seconds in either of the previous steps, the controller

will automatically return to the CURRENT TEMPERATURE display status without modifying

any of the parameters values.

AKO-14918

Power supply

Transfer

Programming

MESSAGES

PA

Password request to enter programming parameters 
or SET POINT

dEF

It indicates defrosting is being carried out. In order to display "dEF" during defrosting,
it is essential that parameter d2 is set to option 2.

AE

Flashing with temperature

- External alarm

AES Flashing with temperature

- Severe external alarm

AH

Flashing with temperature

-Maximum temperature alarm.

Sensor 1 temperature exceeds the parameter programmed in A1.

AL

Flashing with temperature

- Minimum temperature alarm.

Sensor 1 temperature is lower than the parameter programmed in A2.

oFF Unit off

- STANDBY Mode (equipment maintains electric power supply)

CPY

Parameters received from the parameters server.

E1

Sensor 1 failure  (Open circuit, crossed, temp.> 110ºC or temp.<-55ºC

E2

Sensor 2 failure  (Open circuit, crossed, temp.> 110ºC or temp.<-55ºC

ES

Incorrect sensor configuration (See P4, P8)

EE

Memory failure