background image

Device designed to display, control and regulate cooling generators (manual or automatic
programmable defrosting).

1463H202  Ed.03

Surface temperature controller with 3 relays and 2 probes

GB

MODEL

FUNCTION

RELAY

POWER SUPPLY,

50/60 Hz

COOL: 16 A, 250 V, cos 

ϕ

=1, SPST

AKO-14632

Controller

DEF:

8 A, 250 V, cos 

ϕ

=1, SPDT

230 V~ ±10%

FAN:

6 A, 250 V, cos 

ϕ

=1, SPST

1- Versions and references

2- Technical data

Temperature range:. . . . . . . . . . . . . . . . . . . . . -50.0 ºC  to   99.9 ºC  (-58.0 ºF to 211 ºF)
Resolution, Set Point and differential: . . . . . . . 0,1 or 1 ºC/ºF configurable by parameter P7
Input for NTC probe: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

AKO-149XX

Thermometric accuracy: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 1 ºC
Probe tolerance at 25 ºC: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 0,4 ºC
Maximum input power: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 VA
Working ambient temperature:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 ºC to 50 ºC
Storage ambient temperature:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -30 ºC to 70 ºC
Control device classification:
Independent mounting, with characteristic of automatic operation Type 1.B action, to be
used in a clean situation, logical medium (software) class A and continuous operation.
Degree of contamination 2 on UNE-EN 60730-1
Double insulation between the power supply, the secondary circuit and the relay output.
Allocated pulse temperature: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2500 V
Pressure ball test temperature:

Accessible parts: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 ºC

Parts that position active elements:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 ºC

Voltage and current declared by the EMC tests: . . . . . . . . . . . . . . . . . . . .  207 V, 22 mA
Current of radio jamming supression test: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 270 mA

3.1 Fastening

3.2 Connection:

The probe and its lead should 

NEVER

be installed in duc-

ting along with power, control or power supply wiring.
The power supply circuit should be connected with a mini-
mum 2 A, 230 V, switch located close to the unit. Power
supply cables should be H05VV-F 2x0,5 mm

2

or H05V-K

2x0,5 mm

2

.

Section of connecting wires for relays contacts should be
2,5 mm

2

.

3- Installation

The controller should be installed in a place protected from vibrations, water and corrosive
gases, and where ambient temperature does not surpass the value specified in the technical
data.
In order to give a correct reading, the probe should be installed in a place without heat
influences other than the temperature that is to be measured or controlled.

AKO-14632

1

2

4

5

8

3

9

10

11

12

13

14

±

10% 50/60 Hz

COOL

C

DEF

FAN

S1-TEM

S2-DEF

DI1

SONDAS

PROBES

*16A

*8A

*6A

*Imax = 16 A

cos

ϕ

=1  250 V

230V~

In=22mA~

4- Funciones del frontal

LED Cool (Compressor) 
Permanent:

Cooling relay COOL (com-

pressor) energised.

Flashing:

Because of the temperature

detected by Sensor 1 (TEM), the COOL
relay should be energised, but is no due to
a programmed parameter.

LED Fan 
Permanent:

Fan relay energised.

Flashing:

Because of the temperature

detected by Sensor 2 (DEF), the Fan relay
should be energised, but is no due to a pro-
grammed parameter.

LED Def 
Permanent:

Indicates defrost in opera-

tion.

LED Alarm 
Permanent:

Alarm indicator enabled.

Flashing:

Alarm detected, but display

maintained.

LED DT 
Permanent:

Indicates last defrost ended

by time.

LED Continuous cycle
Permanent:

It indicates that the conti-

nuous cycle is active.

LED

Cool

ºC

ºF

LED

Def

LED

ºC

LED

ºF

LED

Continuous

Cycle

DOWN

KEY

LEFT

KEY

SET

KEY

UP

KEY

RIGHT

KEY

LED

Fan

LED

Alarm

LED DT

LED ºC 
Permanent:

Degrees ºC indicator.

Flashing:

Programming phase.

LED ºF 
Permanent:

Degrees ºF indicator.

Flashing:

Programming phase.

UP KEY 

- Press once to cancel the alarms, but they

remain displayed.

- In programming, it makes the displayed

value increase.

- When pressed it displays the help messa-

ge 

dEF

corresponding to the short key

function that it performs.

- When pressed for at least 5 seconds, a

manual 

defrost

is started / stopped with

programmed duration.

DOWN KEY 

- Press once to cancel the alarms, but they

remain displayed.

- In programming, it makes the displayed

value reduce.

- When pressed, it displays the help mes-

sage 

Con

corresponding to the function

performed by the key.

- Pressing during 3 seconds,it activates /

deactivates the 

CONTINUOUS CYCLE

during the time for which it has been
programmed.

RIGHT KEY 

- Press once to cancel the alarms, but they

remain displayed.

- In programming, it makes the level value

increase.

- When pressed, it displays the help mes-

sage 

oFF

corresponding to the function

performed by the key.

- Pressing during 3 seconds it turns off/on

the unit leaving it in 

STAND-BY

. The dis-

play shows 

oFF

when the unit is discon-

nected.

LEFT KEY 

- Press once to cancel the alarms, but they

remain displayed.

- Exit programming level.

KEY

- Press once to cancel the alarms, but they

remain displayed.

- In programming, accept the programmed

new value.

- When pressed it displays the help messa-

ge 

SP

corresponding to the function per-

formed by the key.

- When pressed for at least 5 seconds, the

SP 

Set Point

temperature is displayed.

5- Adjustment and configuration

It should only be programmed or modified by personnel who are fully conversant with the
equipment operation and possibilities.

5.1 Set Point temperature

The factory SET POINT default value is 0.0 ºC.
- Press

key for at least 5 seconds to DISPLAY SET POINT. It displays the CURRENT SET

POINT value and LED ºC or ºF starts flashing.

- Press

or

keys to CHANGE SET POINT into the required value.

- Press

key to ACCEPT THE NEW SET POINT. The display returns to the CURRENT TEM-

PERATURE display status and LED ºC or ºF stops flashing.

- Press the

key to exit the temperature set point without modifying the value.

When 

PA

is displayed, PASSWORD programmed in

L5

parameter of 

tid

menu should be

entered to access the CURRENT SET POINT.
- Press

key.

0

will be displayed to ENTER PASSWORD.

- Press

or

keys to CHANGE NUMBER and DISPLAY PASSWORD programmed.

- Press

key to ACCEPT PASSWORD. The CURRENT SET POINT value will be displayed

and it can be already modified.

5.2 Parameters configuration

Level 1

Menus

When the keys

+

are pressed simultaneously for at least 10 seconds, the display

shows 

Pro

for 10 seconds. LED ºC or ºF will be flashing, we are in the programming LEVEL

1 MENUS and the first menu “

rE

” is displayed.

- Press

key to access the next menu and

key to return to previous one.

- Pressing

key, the controller returns to the CURRENT TEMPERATURE display status and

LED ºC or ºF will stop flashing.

When 

PA

is displayed, PASSWORD programmed in 

L5

of “

tid

” menu should be entered to

access programming LEVEL 1 MENUS.
- Press

key.

0

will be displayed to ENTER PASSWORD.

- Press

or

keys to CHANGE NUMBER and DISPLAY PASSWORD programmed.

- Press

key to ACCEPT PASSWORD. The first menu “

rE

” will be displayed.

171

35

60

94

Ø máx. 3,7

125,5

41,5

Detail of fixing screw-holes.

Suitable fixing screw-holes for universal 

flush-mounting wall box

.

Press down lightly 

to open the cover.

CURRENT

TEMPERATURE

A

CCEPT

PASSWORD

DISPLA

Y

SET POINT

CHANGE SET POINT

A

CCEPT

THE NEW

ENTER

PASSWORD

DISPLAY

PASSWORD

CURRENT

SET POINT

NEW

SET POINT

If  

P2=0

  or  

L5=0

PASSWORD

REQUEST

CHANGE NUMBER

5 Sec.

Отзывы: