5204H401 Ed.01
Input configuration
Allows you to configure the behaviour of the digital inputs.
Send “I(n),
<NC/NO>, <persistence time>, <message>
”
Example:
To configure input 2 as a normally open contact, with a persistence time of 15 seconds and a
customised alert message, send:
After a few seconds, the alarm responds with the message*:
Customisation of power failure message
Change the alert message for power failure or restoration of power.
Send “BATMSG,
<message OFF>,<message ON>
Example:
Send:
After a few seconds, the alarm responds with the message*:
Customisation of the reset message
Change the alert message for the alarm reset.
This message is sent only to the first number on the
telephone list.
Example:
Send “RESETMSG,
<message>
After a few seconds, the alarm responds with the message*:
Send
Send
BATMSG OK
RESETMSG OK
BATMSG,Power failure,
Power has been restored
RESETMSG, The alarm has been reset
<
message
OFF>
Message in the event of power failure
<
message
ON>
Message in the event of power being restored
Send
I2 OK
I2,NO,15,High temperature
in frozen food cold room
<n>
Number of the input to be configured.
<NC/NO>
Defines the input polarity:
NO:
Normally open, the alarm is activated on closing.
NC:
Normally closed, the alarm is activated on opening.
<persist. t.>
Time in seconds that the input must remain active to send an alert.
<message>
Message that will be received if the alarm for the configured input is activated.
20
*If you receive an error message, refer to page 25.