akira AC-S13CG series Скачать руководство пользователя страница 19

 

 

     

19

 

secutive times within 30 minutes, the machine stops, and it must be restarted by 
remote controller. 

f. 

Defrosting conditions and procedures 

i.  In heating mode, if compressor has run 44 minutes ( in its first 6 minutes it will not 

detect defrosting temp.) , and it has detected T con < or = -4

o

C for continuous 1 

minutes, it begins to defrost, electric heater will stop for 10 seconds ( even if 
electric heater is not working), then indoor motor stops, reversing valve becomes 
inactive in another 2 seconds, another 2 seconds later, outdoor motor stops, 
when T con > or = 10

o

C or defrosting lasts for 10 minutes, outdoor motor and re-

versing valve becomes active, indoor motor will run as the anti cool air condition, 
then it cycles again, recalculates the compressor’s running time again. (In this pe-
riod, if any protection works, and after the machine is back to work, it will re-start 
defrosting state. it will not detect outdoor tube temp when compressor’s in its first 
6 minutes running) 

g.  Noise eliminated protection 

i.  When you use RUN/STOP button to switch off the machine, reversing valve will 

become inactive in 2 minutes. 

 

AUTO mode 

 

In AUTO mode, standard cooling T set = 25

o

C, standard heating T set = 20

o

C. 

2 Working 

procedures 

a.  If T indoor > or = T set + 1

o

C , select cooling mode, from this time, the set temp. is 

25

o

C. If T indoor < or = T set – 1

o

C, compressor and outdoor motor stop, indoor mo-

tor runs at the set speed, if T set -1 < T indoor < T set + 1

o

C, keep the original state. 

b.  If T indoor < or = T set + 2

o

C, select heating mode, from this time, the set temp. is 

20

o

C, if T indoor > or = T set + 4

o

C, compressor stops first, outdoor motor stops 15 

seconds later, reversing valve is always active, indoor motor runs as the blowing sur-
plus heat condition. If T set +2

o

C < T indoor < T set +4

o

C, keeps the original state. 

Cooling only AUTO mode: there is no heating function in this mode. 

3 Protections 

a.  It is same as the one in cooling or heating mode. 

 

4 Other 

controls 

1 SWING 

mode 

a.  When it is active, the louver returns to position O, close the air outlet. 
b.  When machine works, it turns to the max. Air output position D, then returns back to 

position L to stand by (position L is the horizontal place mentioned before). 

c.  In swing state, the louver swings between position L and position D. 
d.  When the machine is switched off, it is back to position O. 
e.  When the machine is running and the swing is off, the louver stops at position E. 

 
 
 
 
 
 
 
 
 
 
                                                      O 
 

 

                                               

 
 
Model  No: AC-S13CGx2.doc 

                                            

 
 
 
 
 

Version 1.0 
 

   

 

 

 

 

 

Содержание AC-S13CG series

Страница 1: ...A A Ai i ir r r C C Co o on n nd d di i it t ti i io o on n ne e er r r S S Se e er r rv v vi i ic c ce e e M M Ma a an n nu u ua a al l l ...

Страница 2: ...2 Model No AC S13CGx2 doc 3 Model AC S13CG x 2 Version 1 0 ...

Страница 3: ... Outline dimension of outdoor unit 11 Exploded view of indoor unit 12 Spare parts list of indoor unit 13 Exploded view of outdoor unit 14 Spare parts list of outdoor unit 15 Circuit Diagram 16 PCB Function Manual 17 TECHNICAL SPECIFICATION Content AC S13CG Model No AC S13CGx2 doc Version 1 0 ...

Страница 4: ...Indoor unit Net weight Kg 8 5 Input power W 1179 Current A 5 33 L R A A 29 Throttling method Capillary Compressor RH207VHKC Starting method Capacitor Starting Working temp 115o C 115o C Condenser Aluminum fan copper tube Pipe diameter 9 52 Row fin distance mm 1 1 6 Working area 0 4 Fan motor speed rpm 48 880 Type piece Axial fan 1 Diameter mm 400 Defrosting method Auto defrost Noise dB A 56 Dimens...

Страница 5: ...5 Cooling operation condition In testing indoor and outdoor have same work condition Heating operation Indoor work condition dry bulb temp 21 wet bulb temp 15 5 o C Model No AC S13CGx2 doc Version 1 0 ...

Страница 6: ...6 Model No AC S13CGx2 doc Version 1 0 ...

Страница 7: ...7 Model No AC S13CGx2 doc Version 1 0 ...

Страница 8: ...8 Model No AC S13CGx2 doc Version 1 0 ...

Страница 9: ...9 Model No AC S13CGx2 doc Version 1 0 ...

Страница 10: ...10 OUTLINES AND DIMENSIONS OF INDOOR UNIT Model No AC S13CGx2 doc Version 1 0 ...

Страница 11: ...11 OUTLINES AND DIMENSIONS OF OUTDOOR UNIT Model No AC S13CGx2 doc EXPLODED VIEW OF INDOOR UNIT Version 1 0 ...

Страница 12: ...12 Model No AC S13CGx2 doc Version 1 0 ...

Страница 13: ...012002 1 21 Guide Louver 10512001 1 22 Remote Controller 30512505 1 23 Guide Louver Bearing 10542011 3 24 Air Cleaner B 11012003 1 25 Evaporator Pipe Cover 06122001 1 26 Sensor Insert 42020063 1 27 Stepping Motor MP24GA 15212102 1 28 Motor FN14A 15012108 1 29 Motor Clamp 26112014 1 30 Wire Clamp 71010103 1 31 Pipe Clamp 24242001 1 32 PCB 5K512 30025507 1 33 Tube Sensor 39000165 1 34 Room Sensor 39...

Страница 14: ...14 PARTS LIST OF OUTDOOR UNIT Model No AC S13CGx2 doc Version 1 0 ...

Страница 15: ...Clamp 71010103 2 17 Insulation Gasket 70410525 1 18 Terminal Board T386A 42011241 1 19 Electric Plate 01413425 1 20 Comp Capacitor 30uF 450V 33000021 1 21 Capacitor clamp 02143401 1 22 Fan Capacitor 3uF 450V 33010027 1 23 Terminal Board 2 8 1 24 Isolation Sheet Assy 01233417 1 25 Tube Sensor 1 26 Condenser Assy 01103408 1 27 Rear grill Assy 11123402 1 28 Top cover Assy 01253261 1 29 Motor Support ...

Страница 16: ...16 PCB FUNCTION MANUAL 3 In 1 PCB Function manual A Running mode Model No AC S13CGx2 doc Version 1 0 ...

Страница 17: ...ion a Anti freezing function i If compressor have run 6 minutes and detect T eva 0o C for continuous 3 min utes then the compressor outdoor fan stopped indoor fan run at the set fan speed After 3 minutes later it will run at the original state if T eva or 10o C b Compressor protection i Compressor s starting interval should be more than 3 minutes no matter in what ever modes and conditions If it s...

Страница 18: ...ing range is 16 30o C 3 The working conditions of auxiliary electric heater a In heating mode when compressor is working indoor motor runs at high speed and middle speed If it detect T eva 50o C for continuous 8 seconds and T indoor or 25o C electric heater will work if compressor stop or indoor motor runs at low speed or T eva 54o C or T indoor 28o C or 10 seconds before defrosting the electric h...

Страница 19: ...O mode 1 In AUTO mode standard cooling T set 25o C standard heating T set 20o C 2 Working procedures a If T indoor or T set 1o C select cooling mode from this time the set temp is 25o C If T indoor or T set 1o C compressor and outdoor motor stop indoor mo tor runs at the set speed if T set 1 T indoor T set 1o C keep the original state b If T indoor or T set 2o C select heating mode from this time ...

Страница 20: ...ir 1 ii Press the button AIR on the remote controller to select fresh air 1 function the swing motor keeps running till you give a signal to change it 6 Automatic fan speed a In cooling mode if T indoor T set 5o C high speed T indoor or T set 3o C middle speed T indoor or T set 1o C low speed b In dehumidify mode if T indoor or T set 5o C high speed T indoor or T set 2o C low speed SLEEP mode 1 In...

Страница 21: ......

Отзывы: