secutive times within 30 minutes, the machine stops, and it must be restarted by
remote controller.
f.
Defrosting conditions and procedures
i. In heating mode, if compressor has run 44 minutes ( in its first 6 minutes it will not
detect defrosting temp.) , and it has detected T con < or = -4
o
C for continuous 1
minutes, it begins to defrost, electric heater will stop for 10 seconds ( even if
electric heater is not working), then indoor motor stops, reversing valve becomes
inactive in another 2 seconds, another 2 seconds later, outdoor motor stops,
when T con > or = 10
o
C or defrosting lasts for 10 minutes, outdoor motor and re-
versing valve becomes active, indoor motor will run as the anti cool air condition,
then it cycles again, recalculates the compressor’s running time again. (In this pe-
riod, if any protection works, and after the machine is back to work, it will re-start
defrosting state. it will not detect outdoor tube temp when compressor’s in its first
6 minutes running)
g. Noise eliminated protection
i. When you use RUN/STOP button to switch off the machine, reversing valve will
become inactive in 2 minutes.
AUTO mode
1
In AUTO mode, standard cooling T set = 25
o
C, standard heating T set = 20
o
C.
2 Working
procedures
a. If T indoor > or = T set + 1
o
C , select cooling mode, from this time, the set temp. is
25
o
C. If T indoor < or = T set – 1
o
C, compressor and outdoor motor stop, indoor mo-
tor runs at the set speed, if T set -1 < T indoor < T set + 1
o
C, keep the original state.
b. If T indoor < or = T set + 2
o
C, select heating mode, from this time, the set temp. is
20
o
C, if T indoor > or = T set + 4
o
C, compressor stops first, outdoor motor stops 15
seconds later, reversing valve is always active, indoor motor runs as the blowing sur-
plus heat condition. If T set +2
o
C < T indoor < T set +4
o
C, keeps the original state.
Cooling only AUTO mode: there is no heating function in this mode.
3 Protections
a. It is same as the one in cooling or heating mode.
4 Other
controls
1 SWING
mode
a. When it is active, the louver returns to position O, close the air outlet.
b. When machine works, it turns to the max. Air output position D, then returns back to
position L to stand by (position L is the horizontal place mentioned before).
c. In swing state, the louver swings between position L and position D.
d. When the machine is switched off, it is back to position O.
e. When the machine is running and the swing is off, the louver stops at position E.
O
Model No: AC-S13CGx2.doc
Version 1.0
Содержание AC-S13CG series
Страница 2: ...2 Model No AC S13CGx2 doc 3 Model AC S13CG x 2 Version 1 0 ...
Страница 6: ...6 Model No AC S13CGx2 doc Version 1 0 ...
Страница 7: ...7 Model No AC S13CGx2 doc Version 1 0 ...
Страница 8: ...8 Model No AC S13CGx2 doc Version 1 0 ...
Страница 9: ...9 Model No AC S13CGx2 doc Version 1 0 ...
Страница 10: ...10 OUTLINES AND DIMENSIONS OF INDOOR UNIT Model No AC S13CGx2 doc Version 1 0 ...
Страница 11: ...11 OUTLINES AND DIMENSIONS OF OUTDOOR UNIT Model No AC S13CGx2 doc EXPLODED VIEW OF INDOOR UNIT Version 1 0 ...
Страница 12: ...12 Model No AC S13CGx2 doc Version 1 0 ...
Страница 14: ...14 PARTS LIST OF OUTDOOR UNIT Model No AC S13CGx2 doc Version 1 0 ...
Страница 16: ...16 PCB FUNCTION MANUAL 3 In 1 PCB Function manual A Running mode Model No AC S13CGx2 doc Version 1 0 ...
Страница 21: ......