Model No: AC-S10CG  

                                            

Version 1.0 

 

   

 

 

 

 

 

 
 
 

b.  Anti high temp. 

i.  In heating mode, if it detect T eva 56

o

C (58

o

C can be selected), outdoor motor will 

stop (in this period it will not detect the defrosting temp.). If T eva < or = 52

o

C, 

outdoor motor will be back running (it will not detect defrosting temp. in the first 5 
seconds). 

c.  Blowing surplus heat 

i.  In heating mode, when set temp is reached ,comp. stops first,15 seconds later 

outdoor fan stops, Indoor motor blows 90 seconds (60 seconds can be selected) 
at low speed ,swing motor makes the louver at the horizontal position. 

d.  Compressor’s protection is same with the one in cooling mode. 
e.  Overload protection 

i.  If it detects that the system current surpassed the designed 13 A for continuous 3 

seconds, compressor, electric heater and outdoor motor stop , indoor motor runs 
the same procedures as the blowing surplus heat condition. After 3 minutes and 
current no more than 13 A, the machine will be back to its original state, indoor 
motor runs as the anti cool air condition. If it detects overloading state for 3 
consecutive times within 30 minutes, the machine stops, and it must be restarted 
by remote controller. 

f.  Defrosting conditions and procedures 

i.  In heating mode, if compressor has run 44 minutes ( in its first 6 minutes it will not 

detect defrosting temp.), and it has detected T con < or = -4

o

C for continuous 1 

minutes, it begins to defrost, electric heater will stop for 10 seconds ( even if 
electric heater is not working), then indoor motor stops, reversing valve becomes 
inactive in another 2 seconds, another 2 seconds later, outdoor motor stops, 
when T con > or = 10

o

C or defrosting lasts for 10 minutes , outdoor motor and 

reversing valve becomes active , indoor motor will run as the anti cool air 
condition, then it cycles again, recalculates the compressor’s running time again. 
(In this period , if any protection works ,and after the machine is back to work , it 
will re-start defrosting state. it will not detect outdoor tube temp when 
compressor’s in its first 6 minutes running ) 

g.  Noise eliminated protection 

i.  When you use RUN/STOP button to switch off the machine, reversing valve will 

become inactive in 2 minutes. 

 

AUTO mode 
 

1  In AUTO mode, standard cooling T set = 25

o

C, standard heating T set = 20

o

C. 

2  Working procedures 

a.  If T indoor > or = T set + 1

o

C , select cooling mode, from this time, the set temp. is 

25

o

C. If < or = T indoor T set –1

o

C, compressor and outdoor motor stop, indoor motor 

runs at the set speed, if T set –1

o

C < T indoor < T set + 1

o

C , keep the original state. 

b.  If T indoor < or = T set + 2

o

C , select heating mode, from this time, the set temp. is 

20

o

C , if T indoor > or = T set + 4

o

C, compressor stops first, outdoor motor stops 15 

seconds later , reversing valve is always active, indoor motor runs as the blowing 
surplus heat condition. If T set + 2 < T indoor < T set + 4

o

C, keeps the original state. 

Cooling only AUTO mode: there is no heating function in this mode.   

3  Protections 

a.  It is same as the one in cooling or heating mode. 

 
 
 
 
 
 
 

Все каталоги и инструкции здесь:

 http

:

//splitoff.ru/tehn-doc.html

Содержание AC-S10CG

Страница 1: ...n nd d di i it t ti i io o on n ne e er r r S S Se e er r rv v vi i ic c ce e e M M Ma a an n nu u ua a al l l Большая библиотека технической документации http splitoff ru tehn doc html каталоги инструкции сервисные мануалы схемы ...

Страница 2: ...2 Model No AC S10CG Version 1 0 Model AC S10CG Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 3: ...sion of indoor unit 10 Outline dimension of outdoor unit 11 Exploded view of indoor unit 12 Spare parts list of indoor unit 13 Exploded view of outdoor unit 14 Spare parts list of outdoor unit 15 Circuit Diagram 16 PCB Function Manual 17 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 4: ... 37 Dimension width height depth mm 710 x 250 x 180 Indoor unit Net weight Kg 7 Input power W 890 Current A 4 0 L R A A 18 Throttling method Capillary Compressor PH165 X 1C 8DZC2 Starting method Capacitor Starting Working temp 115o C 115o C Condenser Aluminum fan copper tube Pipe diameter 9 52 Row fin distance mm 1 1 6 Working area 0 3 Fan motor speed rpm 950 Type piece Axial fan 1 Diameter mm 320...

Страница 5: ... PERFORMANCE CURVE The change relation between low pressure operation current and temp Cooling operation condition In testing indoor and outdoor have same work condition Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 6: ...6 Model No AC S10CG Version 1 0 Heating operation Indoor work condition dry bulb temp 21 wet bulb temp 15 5 o C Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 7: ...7 Model No AC S10CG Version 1 0 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 8: ...8 Model No AC S10CG Version 1 0 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 9: ...9 Model No AC S10CG Version 1 0 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 10: ...10 Model No AC S10CG Version 1 0 OUTLINES AND DIMENSIONS OF INDOOR UNIT Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 11: ...11 Model No AC S10CG Version 1 0 OUTLINES AND DIMENSIONS OF OUTDOOR UNIT Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 12: ...12 Model No AC S10CG Version 1 0 EXPLODED VIEW OF INDOOR UNIT Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 13: ...nt Panel 20002035 1 19 Filter 11122006 2 20 Remote Controller 30515002 1 21 Guide Louver Bearing 10542011 3 22 Evaporator Pipe Cover 06122001 1 23 Sensor Insert 42020063 1 24 Stepping Motor MP24GA 15212102 1 25 Motor FN13D 15012045 1 26 motor clamp 26112014 1 27 wire clamp 71010103 1 28 Pipe Clamp 24242001 1 29 PCB 5K91D 30025353 1 30 magnet ring 49010104 1 31 Electric Box Cover 2 20102009 1 32 El...

Страница 14: ...14 Model No AC S10CG Version 1 0 EXPLODED VIEW OF OUTDOOR UNIT Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 15: ...12 Fan motor capacitor 1 5uF 450VAC 33010018 33010018 1 13 Electric box assy 01413034 01413034 1 14 Compressor capacitor 25uF 450VAC 33000017 1 14 Compressor capacitor 30uF 450VAC 33000018 1 15 Terminal board 42011241 42011241 1 16 Wire clip 24253002 24253002 1 17 Wire seat 24253001 24253001 1 18 Capacitor localizer 02113002 02113002 1 19 Capillary assy 03003106 03003194 1 20 One way valve 1 21 Re...

Страница 16: ...Все каталоги и инструкции здесь http splitoff ru tehn doc html 16 ...

Страница 17: ...speed b if T in or T set 1o C the machine stops Compressor stops first outdoor motor stops after 15 seconds indoor motor runs at the set fan speed c if T set 1o C T in T set 1o C keep the previous state 2 In this mode the reversing valve is inactive the temp setting range is from 16 30o C 3 Protect function a Anti freezing function i If compressor have run 6 minutes and detect T eva 0 for continuo...

Страница 18: ...ing mode compressor runs 6 minutes if it detects T eva 0o C compressor and outdoor motor stop indoor motor runs at low speed after 3 minutes delay and T eva or 10o C it will be back to its original state Heating mode 1 The working conditions and control measures a If T in or T set 2o C it goes into heating mode reversing valve compressor and outdoor motor all work in the same time indoor fan will ...

Страница 19: ...for 10 seconds even if electric heater is not working then indoor motor stops reversing valve becomes inactive in another 2 seconds another 2 seconds later outdoor motor stops when T con or 10o C or defrosting lasts for 10 minutes outdoor motor and reversing valve becomes active indoor motor will run as the anti cool air condition then it cycles again recalculates the compressor s running time aga...

Страница 20: ...TO mode indoor motor runs in low speed fresh air function is not active press again the machine stops 5 Digital tube display a the digital tube displays the setting temperature the range is16 30o C when the machine is running b The digital tube displays the setting time the range is 1 24 hours for 5 seconds when remote controller sets timer of on off Then come back to display the setting time time...

Страница 21: ...or or T set 2o C low speed 8 SLEEP mode a In cooling or dehumidifying mode 1 hour after you set the sleep timer T set will add 1o C automatically another 1 hour another 1 will be added b In heating mode 1 hour after you preset the sleep timer T set will lower 1o C auto matically another 1 hour another 1o C will be lowered Большая библиотека технической документации http splitoff ru tehn doc html к...

Отзывы: