c. Overload protection
i. If it detect the system current surpass the designed 13 A for continuous 3 min-
utes, the machine go into fan mode, when 3 minutes passed and it detect the
current no more than 13 A, it will back to original state. If it detects overloading
states for 6 consecutive times, the machine stops, and must be restarted by re-
mote controller.
Dehumidifying mode
1 The working conditions and control measures
a. If T in > T set + 2
o
C , it is in cooling running, the indoor motor speed can be selected,
and outdoor motor run at low speed.
b. If T set –2oC < or = T in < or = T set + 2
o
C ,it goes into dehumidifying running ,the
indoor motor run at the low speed, 6 minutes later the compressor stops, another
15 seconds later the outdoor fan stops and another 30 seconds later, the indoor
motor stops, 3 and a half minutes later, compressor and outdoor fan run again ,indoor
motor runs at the low speed, then the machine cycle the above procedures
repeatedly. outdoor motor runs at the low speed.
c. If T in < T set - 2
o
C, compressor ,outdoor motor and indoor motor stop.
2 In this mode, the reversing valve is inactive , the temp. setting range is 16~30 .
3 Anti-freezing protection.
a. If T indoor > T set + 2
o
C, it goes into cooling running , anti-freezing function is same
with cooling mode, but the compressor must stops for 4 minutes. when it goes into
dehumidifying mode, compressor runs 6 minutes , if it detects T eva < 0
o
C,
compressor and outdoor motor stop, indoor motor runs at low speed ,after 3 minutes
delay, and T eva > or = 10
o
C, it will be back to its original state.
Heating mode
1 The working conditions and control measures
a. If T in < or = T set + 2
o
C, it goes into heating mode, reversing valve, compressor and
outdoor motor all work in the same time, indoor fan will run at the same procedures
with anti cool air function.
b. If T in > or = T set + 4
o
C , compressor stops first, 15 seconds late, outdoor motor
stops, but reversing valve keeps working, indoor motor run at the procedures of
blowing surplus heat.
c. If T set + 2
o
C < T indoor < T set + 4
o
C , keep the previous running state.
2 In this mode, the temperature setting range is 16~30
o
C.
3 The working conditions of auxiliary electric heater.
a. In heating mode, when compressor is working, indoor motor runs at high speed and
middle speed. If it detect T eva < 50
o
C for continuous 8 seconds and T indoor 25
o
C,
electric heater will work, if compressor stop or indoor motor runs at low speed or T
eva > or = 54
o
C or T indoor > or = 28
o
C or 10 seconds before defrosting , the electric
heater will stop.
4 Protections
a. Anti cool air
i. when the machine starts heating and T eva > or = 22
o
C , indoor motor runs at low
speed, and swing motor makes the louver at the horizontal position (in Bird line, it
will swing to the maximum air volume position), if T eva > or = 40
o
C or compres-
sor have run 2 minutes ,indoor motor and swing motor will run at the set speed.
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Содержание AC-S10CG
Страница 7: ...7 Model No AC S10CG Version 1 0 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...
Страница 8: ...8 Model No AC S10CG Version 1 0 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...
Страница 9: ...9 Model No AC S10CG Version 1 0 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...
Страница 16: ...Все каталоги и инструкции здесь http splitoff ru tehn doc html 16 ...