Страница 1: ...ASGC 34 5TL 4P4W User Installation Manual www ait ac at...

Страница 2: ...on procedures for installing the AIT Smart Grid Converter as well as information about operating the converter Organization This manual is organized into the following chapters Chapter 1 Introduction...

Страница 3: ...of delivery 6 Nameplate 6 2 2 Mounting 6 Requirements for the mounting location 6 Permitted mounting positions 7 Recommended clearances 7 Mounting the converter 7 2 3 DC Connection 8 Assembling DC co...

Страница 4: ...creased power handling capability the AIT Smart Grid Converter presents a perfect Smart Grid fit 1 2 Key features Superb handling of arbitrarily unbalanced grid current voltage and load conditions Gri...

Страница 5: ...5 1 3 Physical Features Figure 1 Location of physical features of the converter side view Figure 2 Location of physical features of the converter bottom view...

Страница 6: ...and provides the following information Model name DC input data AC output data Certification 2 2 Mounting Requirements for the mounting location A solid support surface must be available for mounting...

Страница 7: ...of injury if the converter is lifted incorrectly or dropped while being transported or when attaching it to or removing it from mounting surface Transport and lift the converter carefully The service...

Страница 8: ...e that the following requirement is met for installation All the components installed between the DC Source and the converter shall be rated for at least 1000 VDC and as per the applicable installatio...

Страница 9: ...r to secure the DC cables 2 4 AC Connection The converter can be connected either to a grid simulator or directly to the grid An AC breaker is to be used to protect the grid side of the converter Use...

Страница 10: ...5 Nm 0 3 Nm torque 5 Place the contact insert into the sleeve housing 6 Tighten the four screws on the front side of the contact insert with 1 5 Nm 0 3 Nm torque 7 Secure the sleeve housing with a cab...

Страница 11: ...C terminal shown in Figure 2 3 Tighten mounting screws of the AC plug with 1 5 Nm 0 3 Nm torque 2 5 Communication Interface The communication interface resides on Safety Extra Low Voltage SELV potenti...

Страница 12: ...O 9 Digital Output 1 Open Collector DIO 10 Digital Output 1 Common DIO 11 Signal Ground DIO 12 Digital Output 2 Open Collector DIO 13 Digital Output 2 Common DIO 14 Signal Ground DIO 15 Digital Output...

Страница 13: ...up 1 Complete the wiring as described in chapter 2 DC wiring AC wiring 2 Connect the USB cable between PC and the converter SCI port for communication COM port can be validated in the Device Manager F...

Страница 14: ...ation on how to use Typhoon HIL Control Center refer to Typhoon HIL Documentation 4 In Windows Search look for Standalone HIL SCADA which is provided as a part of Typhoon HIL Control Center 5 Load the...